52
SECTION VI - BURNER SPECIFICATIONS
NOTICE
V9A boiler ratings and capacities are based upon the following burners, pump pressures, nozzle sizes and
manifold pressures. Refer to instructions furnished with burner for additional information regarding proper
installation, fuel piping, wiring details, burner adjustments, service instructions and burner start-up.
Boiler
Model
Burner
Input
(GPH)
Burner
Mfr.
Burner
Model
Air Tube
Comb.
Burner Settings
Pump
Pressure (PSI) Nozzle
Make
Nozzle Data
Head
Air
Shutter
Air
Band
Air Damper
Low
Fire
High
Fire
GPH x
Angle-Type
Low
High
V903A
3.1
Beckett
CF-500
CF60KK
2
10
3
N/A
N/A
---
150
Hago
2.50 x 45° - P
V904A
4.2
Beckett
CF-800
CF80KH
1
8
0
N/A
N/A
---
150
Hago
3.40 x 45° - P
V905A
5.6
Beckett
CF-800
CF80KH
2
10
6
N/A
N/A
---
150
Hago
4.50 x 45° - P
V906A
7.0
Beckett
CF-1400
CF66KD
3
N/A
N/A
2.75
4.0
150
300
Hago
4.00 x 60° - P
V907A
8.3
Beckett
CF-1400
CF66KD
4
N/A
N/A
3.0
6.5
150
275
Hago
5.00 x 45° - P
V908A
9.6
Beckett
CF-1400 CF66KEE
1
N/A
N/A
3.5
8.5
150
300
Hago
5.50 x 45° - P
V909A
11.6
Beckett CF-2300A CF66KG
0
N/A
N/A
2.0
4.0
150
275
Hago
7.00 x 45° - P
V910A
13.2
Beckett CF-2300A CF66KG
1
N/A
N/A
2.0
6.0
150
275
Hago
8.00 x 45° - P
V911A
14.8
Beckett
CF-2500
CF66KP
0
N/A
N/A
0.5
3.0
275
275
Hago
(L) 4.50 x 45° - P
V912A
16.4
Beckett
CF-2500
CF66KP
0
N/A
N/A
0.5
4.0
275
275
Hago
(H) 5.00 x 45° - P
Table V: Beckett Burner Specifications
OIL BURNERS
GAS BURNERS
Boiler
Model
Burner
Input
(MBH)
Burner
Mfr.
Burner
Model
Damper Settings
Manifold Pressure - “W.C.
Minimum Inlet Pressure
- “W.C.
Low
Fire
High
Fire
Shutter Band
Low Fire
(Start)
High Fire
V903A
447
Beckett
CG10.1S
---
---
10
1
(1.3)
2.5
3.24
V904A
606
Beckett
CG10.4S
---
---
5
2
(1.3)
2.6
3.64
V905A
808
Beckett
CG10.5S
---
---
7
1
(1)
3.3
4.61
V906A
1010
Beckett
CG10.6S
---
---
10
6
(1.1)
3.64
5.43
V907A
1198
Beckett
CG15.3S
18
43
---
---
0.9
3.1
5.31
V908A
1386
Beckett
CG15.4S
21
63
---
---
0.95
3.3
6.14
V909A
1674
Beckett
CG25.2S
23
47
---
---
0.8
3.43
4.69
V910A
1905
Beckett
CG25.3S
26
52
---
---
0.8
3.44
4.94
V911A
2136
Beckett
CG25.4S
28
58
---
---
0.8
3.0
4.88
V912A
2367
Beckett
CG50.2S
10
25
---
---
0.8
2.1
3.87
Summary of Contents for operating and
Page 2: ...2 ...
Page 8: ...8 Section I General Information Figure 1 Dimensional Information ...
Page 21: ...21 Figure 16 Bare Boiler Assembly ...
Page 25: ...25 Figure 22 V9A Series Jacket Assembly Boiler Models V903A thru V912A ...
Page 31: ...31 Figure 26 V9A Series Minimum Piping Parallel Water Boiler ...
Page 32: ...32 Figure 27 V9A Series Minimum Piping Primary Secondary Water Boiler ...
Page 33: ...33 Figure 28 V9A Series Minimum Piping Details Bypass with Blend Pump Water Boiler ...
Page 34: ...34 Figure 29 V9A Series Minimum Piping Primary Secondary with Bypass Water Boiler ...
Page 37: ...37 Figure 32 Minimum Piping Requirements For Gravity Return V9A Series Steam Boilers ...
Page 42: ...42 Figure 37b DHW Generation with Tankless Coils Storage Tank and Destratification Pump ...
Page 43: ...43 Figure 37c DHW Generation with Indirect Water Heater ...
Page 58: ...58 Figure 40 Bare Boiler Assembly ...
Page 62: ...62 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 63: ...63 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 64: ...64 ...