37
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
pellet feed. We recommend the setting to
be
35%
of the main mode. You can change
the pellet feed quantity
(Feed)
in
%
of the
set value at maximum power, and the
power of both fans: the burner fan
(FanB)
and the exhaust gas fan
(FanE)
.
Select the desired option using the
navigation arrows. Use the „
Enter
” button
to open the next parameter.
Auto Clean Setup
12:00
18:00
00:00
06:00
06:00
21:00
Use this menu to adjust
the automatic cleaning
of burner and boiler
Set the time and the
number of automaticsystem cleaning
(Clean Count). At least one cleaning per
24-hour period is required.
Maximum cleanings - not more than six
times per 24-hour period.
Select the desired option using the
navigation arrows. Use the „
Enter
” button
to open the next parameter.
This menu is not active
at the moment.
Does not affect the
boiler operation.
Use this submenu to
activate (with check
mark) or deactivate
additional peripherals.
CH PUMP
– central heating pump
DHW PUMP
– domestic hot water pump
Thermostat
.
Select the desired option using the
navigation arrows. Use the „
Enter
” button
to open the next parameter.
From this screen menu
you can choose the
boiler
operation
management
mode.
This menu is valid only
in the event of "CH only" option selected.
By selecting the checkmark "Buffer" the
boiler will be controlled according to
temperature inside the buffer tank
connected to the boiler. The setting of the
temperature of the buffer tank circulation
pump start and stop temperatures is done
as described above. When selecting the
boiler management via thermostat
option the boiler will be controlled by the
signal input from the thermostat, whereas
the options are: thermostat normally
open or thermostat normally closed. Its
type is introduced at a later step on the
controller menu.
In this menu you can
select the type of the
thermostat used (if that
option is selected)
NO
- normally open;
NC
- normally closed.
From this menu, the
following parameters
are configured:
The
dT
parameter sets
the temperature difference of exhaust
gases upon which the controller should
register ignition. The start point of
watching this difference is the moment of
start of the main burner fan in the process
of ignition. From that point on whenever
the temperature of the exhaust gases in
the boiler rises with 5 degrees an ignition
shall be registered and the boiler will go
into normal operating mode.
The next parameter
> 095°C/30 min
.
determines the time after the boiler shift
to normal operating mode during which
the boiler must exceed the specified
temperature of exhaust gases. Upon
fulfillment of this condition the boiler will
register itself in normal working mode.
If the exhaust gases temperature drops
below
85 °C
the boiler will shift into
extinguishing mode
(Error Burnout)
.