Technical data
Product manual 2CKA001473B8289
│
11
5
Technical data
Nominal voltage
1094...
1095...
1097...
230 V AC ±10%, 50 / 60 Hz
1096...
24 V AC ±10%, 50 Hz
Switching capacity
1094...
1095 U
1095 UTA
10 (A) A, 230 V AC
1096...
16 (2) A, 230 V AC
1096...
1 (1) A, 24 V AC
1096...
5 (2) A, 230 V AC
Connecting terminals
1094...
1095 U
1095 UTA
1096...
1097...
1.5 mm² - 2.5 mm²
1095 UF
2 x 2.5 mm² – 1 x 4 mm²
Temperature adjustment range
1094...
1095 U
1095 UTA
1096...
1097...
1 - 6 (5 - 30°C)
1095 UF
1 - 6 (10 - 50°C)
Temperature reduction
4 K
Switching temperature difference
±0.5 K
Protection type
IP 20 (EN 60529)
Remote sensor 1095 UF
NTC 10 kΩ / 25°C
Sensor line length 1095 UF
4 m
Ambient temperature range
0 - 30°C
Mode of operation (DIN EN
60730-1)
1B
Degree of contamination (DIN EN
60730-1)
2
Rated surge voltage (DIN EN
60730-1)
4000 V