Connection, installation / mounting
Product manual 2CKA001473B8289
│
12
6
Connection, installation / mounting
Danger - Electric voltage!
Risk of death due to electrical voltage of 100 … 240 V during short-circuit in the
low-voltage conduit.
– Low-voltage and 100 … 240 V conduits must not be installed together in a
flush-mounted box!
6.1
Requirements for the electrician
Danger - Electric voltage!
Install the device only if you have the necessary electrical engineering
knowledge and experience.
■
Incorrect installation endangers your life and that of the user of the electrical
system.
■
Incorrect installation can cause serious damage to property, e.g. due to fire.
The minimum necessary expert knowledge and requirements for the installation
are as follows:
■
Apply the "five safety rules" (DIN VDE 0105, EN 50110):
1. Disconnect
2. Secure against being re-connected
3. Ensure there is no voltage
4. Connect to earth and short-circuit
5. Cover or barricade adjacent live parts.
■
Use suitable personal protective clothing.
■
Use only suitable tools and measuring devices.
■
Check the type of supply network (TN system, IT system, TT system) to
secure the following power supply conditions (classic connection to ground,
protective earthing, necessary additional measures, etc.).