112/240
(Tab
Physical address
)
Parameter
KNX --> IP Repetition of group telegrams
is
used to block or enable the repetition of physically addres-
sed telegrams.
If errors occur on the KNX --> IP Repetition of group te-
legrams during the transmission of physically addressed
telegrams (e.g. programming of an application or for di-
agnostics purposes during an inquiry of the state of a devi-
ce), the KNX telegrams are repeated up to three times.
19.5.2.5
IP --> KNX Repitition of
broadcast telegrams
(Tab
Broadcast
)
Parameter
IP --> KNX Repetition of broadcast telegrams
is used to block or enable the repetition of Broadcast tele-
grams
. If errors occur on the Main or Area line during the trans-
mission of broadcast telegrams (e.g. telegrams that are sent
via the KNX multicast address), the KNX telegrams are
repeated up to three times.
19.5.2.6
KNX --> IP Repitition of
broadcast telegrams
(Tab
Broadcast
)
Parameter
KNX --> IP Repetition of broadcast telegrams
is used to block or enable the repetition of Broadcast tele-
grams.
If errors occur on the Sub line during the transmission of
broadcast telegrams (e.g. telegrams that are sent via the
KNX multicast address), the KNX telegrams are repeated
up to three times.
19.5.3
Transfer of telegrams
19.5.3.1
IP --> KNX Group telegrams
main group 14+15
(Tab
Basis
)
The parameter
IP --> KNX Group telegrams main group
14+15
is used to block or enable the transfer of group te-
legrams with the main group addresses 14 and 15 from the
main/area line to the sub line.
Under the
Filter
selection, only the telegrams with the
main group addresses 14 and 15 are transferred that are in
Summary of Contents for Busch-ComfortTouch
Page 1: ...Product manual Busch ComfortTouch Busch ComfortTouch www BUSCH JAEGER de ...
Page 16: ...16 240 ...
Page 147: ...147 240 03_03_09_00_EN html Logikbausteine ...
Page 155: ...155 240 03_03_09_00_EN html Logikbausteine 03_03_09_00_EN html Boolean ...
Page 217: ...217 240 03_03_09_00_EN html weitere_math 03_03_09_00_EN html weitere_math ...
Page 226: ...226 240 03_03_09_00_EN html Signalkontrolle ...