Busch-easycare
®
Connections and commissioning
Technical manual 0073-1-8701
│
30
6.1.1
Output terminals (5) 24 V DC/6 A
The uninterruptible power supply provides a controlled output voltage of 24 V DC,
max. 6 A.
If a load current of approximately 6.8 A is exceeded, the output voltage reduces
at a constant current according to the resistance value of the connected overload.
Connect the load to terminals "+24 V" and "0 V" (provided twice).
»
6.1.2
Signalling outputs (2) and LED displays (1)
The five signalling terminals (1 - 5) on the 7-pole terminal (2) use potential-free
relay contacts to indicate the device status. These contacts may be subjected to
a maximum load of 30 V DC/1 A.
LED lights up
Status
Output
voltage status
Switched
contacts (NO)
Green, "24V DC"
Mains operation
+24 V DC
3 - 5
Yellow, "Battery active"
Battery operation
+20 V
1)
- 24 V DC
3 - 4
Yellow, "Battery active" and
red, "Battery low"
Battery empty
-
3 - 2
Red, "Battery low"
(checked every 15 minutes)
Battery defective
-
3 - 2
(checked every
15 minutes)
Red, "Output Failure
Fuse F2"
F2 failure. Output fuse
F2 has been removed
or is defective.
0 V
-
Tab.2: Signalling outputs and LED displays
1)
At an output voltage of around 20 V, the uninterruptible power supply automati-
cally switches off completely (total discharge protection).