KNX control elements and application parameters
"Switch" control element
Product manual 2CKA001473B5342
│
114
–
Pressing/releasing
: Pressing = value 1; releasing = value 2.
The following supplementary parameters are available, see chapter “Object type 1 / value 2“
on page 114:
–
Object type value 1
: When actuated (pressing) the control element sends telegrams via
the associated communication object. This parameter is used to specify the size of the
communication object.
–
Object type value 2
: When actuated (releasing) the control element sends telegrams via
the associated communication object. This parameter is used to specify the size of the
communication object.
–
Short/long
: Short press = value 1; long press = value 2.
The following supplementary parameters are available, see chapter “Object type 1 / value 2“
on page 114:
–
Long operation after...
:
Options:
Setting option from 0.3 - 10 seconds
The parameter is used to specify how long the button must be pressed to recognize a
long operation.
–
Object type value 1
: When actuated (short press) the control element sends telegrams
via the associated communication object. This parameter is used to specify the size of
the communication object.
–
Object type value 2
: When actuated (long press) the control element sends telegrams
via the associated communication object. This parameter is used to specify the size of
the communication object.
10.1.6 Object type 1 / value 2
Options:
Inactiv
Switch
Forced operation
1-byte value [0% - 100%]
1-byte value [0 - 255]
1-byte value [-128 - 127]
Scene number
RTC operating mode
Temperature
2-byte value [-32768 - +32767]
2-byte value [0 - 65535]
2-byte floating point
4-byte value [-2147483648 - 2147483647]
4-byte value [0 - 4294967295]
14-byte text
Parameters "Object type value 1" and "Object type value 2" are used to specify the size of the