KNX control elements and application parameters
Application "Logical functions"
Product manual 2CKA001473B5342
│
223
Inverting an input
:
Options:
Deactivated
Activated
The parameter is used to specify whether the switching input is inverted.
Filter function
:
Options:
Do not filter
Filter 0
Filter 1
See the explanation above.
–
Forced operation
: Management systems can access the device directly via KNX.
However, it can also be specified that one can select manually (forced operation) via
buttons. No additional parameters available.
–
1-byte value [0% - 100%]
: A value is sent as 1-byte value without a sign (percentage
value). No additional parameters available.
–
1-byte value [0 - 255]
: A value is sent as 1-byte value without a sign, e.g. actuating
value, angle or brightness value. No additional parameters available.
–
1-byte value [-128 - 127]
: A value is sent as 1-byte value with a sign, e.g. actuating
value. No additional parameters available.
–
Scene number
: The parameter is used to link the channel with a scene number. No
additional parameters available.
–
RTC operating mode
: After actuating the control element the device switches to the
parameterized operating mode. No additional parameters available.
–
Temperature
: After the control element is actuated, the device sends the parameterized
temperature value. No additional parameters available.
–
2-byte value [-32768 - +32767]
: A value is sent as 2-byte value with a sign, e.g.
actuating value or time difference. No additional parameters available.
–
2-byte value [0 - 65535]
: A value is sent as 2-byte value without a sign, e.g. actuating
value or time interval. No additional parameters available.
–
2-byte floating point
: A value is sent as 2-byte floating point value, e.g. a temperature
value, a time duration, a power or a consumption value. No additional parameters
available.
–
4-byte value [-2147483648 - 2147483647]
: A value is sent as 4-byte value with a sign,
e.g. actuating value or time difference. No additional parameters available.
–
4-byte value [0 - 4294967295]
: A value is sent as 4-byte value without a sign, e.g.
actuating value. No additional parameters available.
–
14-byte text
: Makes it possible to send a text. No additional parameters available.
Saving input signal during blocking
:
Options:
Deactivated
Activated
See the explanation above.
–
Temperature comparator
: This function can be used to compare temperature values. The
following parameters are displayed:
Type of comparator
: