KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
244
10.24.38 Basic stage cooling
Notice
Only available when the "Extended settings" parameter under "Cooling control"
is activated.
10.24.39 Basic stage cooling — Status object cooling
Options:
Deactivated
Activated
This parameter enables the "Status cooling" communication object.
10.24.40 Basic stage cooling — Mode of the control value
Options:
Normal
Inverse
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
– N
ormal
: Value 0 means "Valve closed".
–
Inverse
: Value 0 means "Valve open".
10.24.41 Basic stage heating - Control value difference for sending of heating control value
Options:
2%
5%
10%
Send cyclic only
The control values of the 0 - 100% PI continuous controller are not transmitted after every
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value to make a transmission meaningful. This value difference
can be entered here.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off“ or "Fan coil".
10.24.42 Basic stage cooling — Cyclic sending of the control value
Options:
00:01:00 - 01:00:00
The current control value used by the device can be cyclically transmitted to the bus.