KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
246
cooling medium will flow through the cooling area to prevent the floor from heating up. Under
"Settings of basic load", it is also possible to define whether this basic load will be permanently
active or whether it will be switched by the "Basic load" object.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".