KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
266
10.24.109
Temperature reading — Weighting of external measurement 2 (0 to 100%)
Options:
Setting option between 0 - 100
Specifying the weighting of the external measurement 2 from 0 to 100%. The setting together
with the weighting of the external measurement (0 - 100%) must result in 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "2x external measurement" or "Internal and 2x
external measurement".
10.24.110
Temperature reading — Cyclic sending of the actual temperature (min)
Options:
Setting option between 5 - 240
The current actual temperature used by the device can be cyclically transmitted to the bus.
10.24.111
Temperature reading — Difference of value for sending the actual temperature
Options:
Setting option between 0.1 - 10
If the change in temperature exceeds the parameterised difference between the measured
actual temperature and the previous actual temperature that was sent, the changed value will
be transmitted.
Notice
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
10.24.112
Temperature reading — Adjustment value for internal temperature measurement
Options:
Setting option between -25 - 25
Every installation location has different physical conditions (interior or exterior wall, lightweight
or solid wall, etc.). In order to use the actual temperature at the installation location as a
measured value for the device, a temperature measurement must be performed by an external
equalised and / or calibrated thermometer at the installation location. The difference between
the actual temperature displayed on the device and the actual temperature determined by the
external measurement device must be entered in the parameter field as an "Adjustment value".
Notice
■
The calibration measurement should not be carried out immediately after
the device has been installed. The device should first adjust to the
ambient temperature before calibration is carried out. The calibration
measurement should be repeated shortly before or after the room is
occupied.
■
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
10.24.113
Temperature reading — Monitoring of temperature reading