KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA001473B5342
│
274
10.24.133
Summer compensation - (Lower) Starting temperature for summer compensation
(°C)
Options:
Setting option between 10 - 40
The parameter is used to specify the lower outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.134
Summer compensation - Offset of the setpoint temperature for the entry into
summer compensation
Options:
Setting option between 0 - 25
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the lower temperature value is reached.
Typical values for summer compensation are:
■
20°C: lower outside temperature value
■
32°C: upper outside temperature value
■
0 K: lower setpoint offset
■
4 K: upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.135
Summer compensation - (Upper) exit temperature for summer compensation
Options:
Setting option between 10 - 40
The parameter is used to specify the upper outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
10.24.136
Summer compensation - Offset of the setpoint temperature for the exit from
summer compensation