Battery Connections
:
Connect black #4 cable from inverter to battery using supplied hardware:
1.
Connect negative cable between negative terminal of inverter and negative terminal
of the battery.
2.
Connect positive cable between positive terminal of inverter and positive terminal of
the battery with 100 amp fuse in line.
Multiple Batteries
: For two or more batteries, batteries must be connected in
parallel
, connecting
batteries in series
will
result in damage to the power inverter.
1.
Connect negative terminal of first battery to negative terminal of second battery.
2.
Connect positive terminal of first battery to positive terminal of second battery.
NOTE:
Batteries are shipped in a separate package. Fuse is already installed on positive battery
cable.
CAUTION: Connect battery only after commercial power is connected and turned on to
the device. Connecting battery before commercial power is turned on could result in
device moving and possibly injuring persons or causing damage to property.
Battery Selection Guidelines
SBBI recommends 12VDC “Maintenance Free” (sealed) batteries without individual cell caps.
NOTE: Your distributor can supply a battery, at extra cost, if you request it.
Gate Operating Modes determine the battery capacity.
GATE OPEN at power fail
18 amp hour (minimum)
GATE SECURE at power fail
1 Operator
2 Operators
20 Gate Cycles
26 amp hours
50 amp hours
40 Gate Cycles
50 amp hours
100 amp hours
NOTE:
A cycle is defined as opening and closing of the gate. Above data requires fully charged battery
and temperatures above freezing (32 degrees Fahrenheit). For other applications contact Byan Systems,
Inc..