Characteristics:
Adjustable Timing Potentiometers:
Color
Description
Minimum Time
Maximum Time
Green
Automatic Closing Timer
1 Second
1 Minute 30 Seconds
Blue
Opening Timer
3 Seconds
30 Seconds *
Red
Closing Timer
3 Seconds
30 Seconds *
*With DIP Switch 1 on S2 turned on, the maximum open and close times are doubled to 1 Minute.
DIP SWITCHES:
Table S1
Number
Option Name
Option Description
1
Reversing Stroke
Function
When turned on, the operators will first close for 1 second
before opening.
2
Step-by-step Function
When turned on, each movement of the operators by any
reverse input will require an individual input (deactivates
automatic re-open function).
3
Automatic Closing
Function
When turned on, the operators will close by the time set
with the green timing potentiometer.
4
Reverse Button
Inoperative During
Opening
When turned on, any reverse input is deactivated during
the open cycle.
5
Closing Order by Car
Safety Contact
With DIP switch 3 off and 5 turned on, the operators will
close as soon as the car safety contacts are cleared.
6
*See Below
*See Below
7
Car Safety Contact
Operative During
Opening
When turned on, car safety contacts are active during the
open and close cycles. Input safety for vehicles only
works on closing movement unless Switch 7 is set ON.
*The function of DIP switch 6 is changed by the position of the jumper (JP1) located below the radio receiver card (J3).
Table S1a describes the function of DIP switch 6 and its relation to JP1.
Table S1a
JP1 Open
JP1 Closed
DIP Switch 6
ON
When power is applied to the board,
operators will automatically perform
a closing function.
The traffic light card will act as a
flashing light card (upper relay) and
a garage light card (lower relay).
DIP Switch 6
OFF
When power is applied to the board,
the operator will automatically
perform an opening function.
The traffic light card relays will act
as a green light (upper relay) and a
red light (lower relay).
Table S2
Number
Option Name
Option Description
1
Double Timing
When turned on, maximum opening and closing time is extended
from 30 Seconds to 1 Minute and maximum pause time is
extended from 45 Seconds to 1 Minute 30 Seconds.
2
Repositioning
the Gate
When turned on, the operators will cycle in the last direction of
operation for 2 seconds every hour