LL CAMD1 MANUAL // REV: 2 // October 25, 2022   

C-Aire 

CAMD1 Owner’s Manual 

Page 

1

 of 

2

 

 

CAMD1 Automatic Air Pressure Maintenance Device

Product Description 

C-Aire's CAMD1 Air Pressure Maintenance Device is an 
automatic,  field-adjustable  device  of  the  pressure 
reducing  type.  It  is  used  to  control  the  supervisory  air 
pressure  in  a  dry  pipe  sprinkler  system,  pre-action 
system,  or  dry  pilot  line  system  of  a  dry  pilot  sprinkler 
actuated  deluge  or  pre-action  valve.  The  CAMD1  is 
utilized in applications where there is a compressed air (or 
nitrogen)  source  which  is  at  a  higher  pressure  than  the 
desired system pressure. Pressure sources include plant 
air  supplies  having  their  own  automatic  compressor 
controls, or nitrogen supplies having single stage cylinder 
mounted pressure regulators. 

The 

½” valve is  opened  to admit air speedily to  the  dry 

pipe  system,  also  known  as  bypass  mode.  It  is  closed 
once  the  desired  system  air  pressure  has  been 
established. As pressure drops on the system side of the 
¼" check valve, the regulator and metering orifice operate 
automatically  to  replace  small  losses  of  air  which 
periodically  occur  in  the  system  due  to  temperature  or 
other  system  variations.  The  regulator  and  metering 
orifice limit the volume of air introduced to assure that the 
rate of air replacement is less than that from an operated 
sprinkler so that system activation may take place. 

Technical Data 

Approval

 

FM 

Maximum Pressure 

 

175 psi 

Pressure Output Range

 

5-60 psi 

End Connections 

 

½

” Female NPT 

Physical Specifications

 

Width: 9

” 

Height: 8

½” 

Weight: 3 lbs.

 

All Valves Vertical = Normal Operation 
All Valves Horizontal = 

Bypass

 Mode 

Installation 

The C-Aire CAMD1 must be installed in accordance with 
the following instructions. 

Make connections a minimum of 

½” pipe size between the 

inlet air supply and the CAMD1, as well as between the 
CAMD1 and the system to pressurize. 

Remove 1/8” NPT plug from regulator and install pressure 
gauge.  Plug  may  be  re-installed  after  setting  system 
pressure. 

Bypass Mode Operation 

1.  Determine desired system pressure. 

a.  Consult  dry  pipe  valve  manufacturer  for 

assistance determining system pressure. 

2.  Turn  all  ball  valve  handles  to  the  horizontal 

position to enter bypass mode. 

3.  Fill  system  to  approximately  5  PSI  less  than 

desired system pressure. 

4. 

Return  ½”  ball  valve  handle  to  vertical  position 
(closed)  and  proceed  to  setting  system  pressure 
procedure. 