C&K Securitech

2

FACTORY DEFAULTS

User / Customer Code 1

1234

Engineer Code

7890

Circuit 1

Personal Attack (PA)

Circuit 2

Alarm circuit

Circuit 3

Alarm circuit isolated in home set

Circuit 4

Alarm circuit with walkthrough

Circuit 5

Entry / Exit circuit

Full set exit time

30 seconds

Night set exit time

15 seconds

Entry time

30 seconds

Bell ring time

15 minutes

These programming defaults are what the panel will revert to if a factory reset is
performed. The panel should come to you programmed in this way however if for
some reason you find it not to be the same, simply perform a factory reset and
this will revert the panel to the above settings.

SPECIFICATION FOR SOFTWARE REVISION NUMBER

V3.0

The software revision number can be located on the top of the main processor

Power Supply

Mains Supply Voltage            

230 v AC Nom

PSU output voltage   

                   

13.6 v DC Nom

Maximum output current       

   

1 amp (total)

Aux current                             

500 mA Max.

Battery Fuse                            

1 A (20 mm)

Panel Quiescent                 

40 mA

Maximum Cable Run 100 Metres

General

Operating temperature           

10 to 50 degrees centigrade

Humidity                                

Up to 80% non condensing

Dimensions                              

304 mm (W)

                                                

220 mm (H)

                                                

89 mm (D)

Control Panel Weight            

1.45  kg Excluding Batt

Stand by Battery                        

2.6 Ah 12 v Rechargeable

                                                

6 Ah max.

Summary of Contents for ACTIVE 5

Page 1: ...ACTIVE 5 ENGINEERING MANUAL C K Systems Ltd C031 066 Issue 3...

Page 2: ...the alarm system Up to 3 remote keypads can be used on the system The positioning of these should be agreed with the user once the entry exit routes and the Part Set functions have been explained to t...

Page 3: ...however if for some reason you find it not to be the same simply perform a factory reset and this will revert the panel to the above settings SPECIFICATION FOR SOFTWARE REVISION NUMBER V3 0 The softwa...

Page 4: ...cable must be separate to all other wiring The cable MUST be earthed and we recommend power is taken from a 3 Amp fused spur and wired by a qualified electrician 2 Battery connection The Active 5 req...

Page 5: ...m the AUX 12 6 Internal sounders Speaker The control panel is fitted with a 35 Ohm speaker in the housing to aid in audible alarms If an extra speaker s is required it should be connected to the termi...

Page 6: ...be fitted mark the holes for the mounting position 2 Screw the backbox in the agreed position 3 Note the rear entry of cabling WIRING A REMOTE KEYPAD 1 The remote keypads require 6 core cable for the...

Page 7: ...ur contact or shunt lock needs to go between S2 and the right hand terminal of the exit zone LINE FAULT INPUT If you are using the Active 5X which is a comms version of the Active 5 control panel you...

Page 8: ...nds whereby the panel will jump out of engineering mode automatically Pressing the HASH key will manually exit engineering If for any reason you need to return to engineering mode you can enter your e...

Page 9: ...4 will light up This has been preset for factory default at 15 minutes A new time may be programmed by entering the keys which when totalled up come to the desired time Once program is set Press to c...

Page 10: ...ion In the day condition visual indication may be programmed option 7 4 1 FULL SET ENTRY ZONE This zone type controls the entry and exit to and from the alarm system When the control is armed tripping...

Page 11: ...be selected with alarm type zones This will make the zone in operative during the Night set arming period Night set arming cannot be selected until one zone has had this option selected WALK THROUGH...

Page 12: ...und Follow this procedure for all or any zones you want to program NOTE All entry zones are isolated in home set Full set entry acts as normal alarm in night set Night set entry acts as normal alarm i...

Page 13: ...system may only be reset by the installer or his representative Entry of the Engineer code is required befo re the system will set again 72 2 Eng only PA reset Following a PA alarm which has been rem...

Page 14: ...R H H RTN ACTIVEGUARD STB S 12V 12V RIGHT HAND TAMPER ACTIVE GUARD 3 ST SW V V RET SECURIGUARD STROBE S SUPPLY SUPPLY LEFT HAND TAMPER NOVA GUARD 2 T STROBE S 12V 12V R SPIRIT AU1000 STB TRG HOLD OFF...

Page 15: ...ROPEAN OPTIONS BATTERY VOLTAGE V AUX VOLTAGE V INSTALLED BY THIS INFORMATION SHOULD BE KEPT EITHER INSIDE THE CONTROL PANEL OR WITH THE INSTALLER IT CAN BE USED TO REFER TO PROGRAMMING DETAILS WHEN NE...

Reviews: