C&K Securitech
6
i)
Timed exit can be used by simply programming the time you wish using the 3-0
and 3-3 options.
ii)
Exit terminate is achieved by connecting the push button across S+ and S2 and
program option 7-3-1 from engineering mode. Make sure you link S1 to S+. This
will stop the panel seeing a telephone line fault.
When the push button is pressed the panel will omit an chime tone, the exit tone
will continue for a further 8 seconds, then the chime tone will sound again, the
system is now set. The chime tone is suppressed in night set. Infinite exit time is
possible for full set only, by setting the exit time to zero (option 3-0-0).
iii)
Door sense setting is achieved in a similar way to exit terminate. You will still
require the link between S1 and S+. You also need option 7-3-1 programmed.
Your contact or shunt lock needs to go between S2 and the right hand terminal
of the exit zone
LINE FAULT INPUT
If you are using the Active 5X which is a comms version of the Active 5
control panel, you will be able to utilise the line fault terminals. These are a pair
of contacts which should be connected to a relay output of a communicator.
They will need to be wired between S1 and S+
ALARM OUTPUTS.
* Timed audible alarm relay. form C rated 2.5A for external sounder.
* Strobe output. Open Collector. Latched until user resets the panel.
300mA output capacity.
* Internal sounder speaker 35 Ohm & output for 2 x 16 ohm max. To follow
all keypad sounds except keypad depression confirmation beeps.
* Latched Fire alarm voltage trigger. High going low in alarm. Restore on
system reset. 5mA at 12v DC.
* Latched panic alarm voltage trigger. Output high going low in
alarm. Restore when system is reset. 5mA at 12v DC.
* Latched alarm voltage trigger. Output high going low in alarm
Restore when system is reset. 5mA at 12v DC