PN 060914-000

Revision C, October 2001

Page 2-11

©  2001,  C-COR.net  Corporation

DLP-502

Page 1 of 3

INTEGRATED FAN/POWER SUPPLY WIRING

Summary:

 The Integrated Fan/Power Supply assembly HW-PSFAN-x-xxx provides AC/DC pri-

mary power conversion and fan cooling for Optiworx products that operate on -48 VDC. It is specifi-

cally used to provide power to a single HWX Equipment Shelf (HX1281EC or HX2281EC).

 

This proce-

dure provides instruction for connecting office ground to the assembly, and wiring of the -48 VDC

power to the HWX Equipment Shelf.

Warning:

  To  prevent  electrical  shock,  never  install  electrical  equipment  in  a  wet

location  or  during  a  lightning  storm.

Caution:

  The  dual  supply  version  of  the  Integrated  Fan/Power  Supply  (HW-PSFAN-2-110)

is designed to provide two (2) power supply sources for 

one 

(1) HWX equipment shelf.

DO  NOT  attempt  to  connect  this  power  supply  to  more  than  one  equipment  shelf.

1. Obtain  the  following  tools  and  equipment:

• Flat-blade or Phillips screwdriver to match terminal block screws
• Ground wire, 16 AWG (minimum), stranded conductor, length as required
• DC power wire, 18 AWG (minimum), stranded conductor, length as required
• Insulated  fork/spade  crimp  terminals,  to  accommodate  18  AWG  wire

(6 for a single output, 12 for redundant)

• Approved  crimp  tool

Warning:

  Steps  2  through  4  connect  the  Integrated  Fan/Power  Supply  to  office

ground.  This  connection  must  be  made  using  methods  and  hardware  that  meet  all

applicable  local  and  national  electrical  codes.

2. Using only the length needed to reach the office ground connection point (wire length

to  be  as  short  and  straight  as  possible),  cut  one  length  of  16  AWG  wire.  Strip  the

insulation from the last 1/2 inch of wire.

3. Press the Integrated Fan/Power Supply spring-loaded ground post (see Figure 502-1) until

the outer and inner sleeves are aligned so that the holes for the wire are matched, then

insert one end of the stripped ground wire into the holes, and release the ground post.

4. Route  the  wire  and  connect  its  other  end  to  the  office  ground  conductor.  Dress  and

secure  the  ground  wire  so  that  it  cannot  come  into  contact  with  any  other  electrical

terminations.

Summary of Contents for Optiworx HW Series

Page 1: ...IntegratedFan PowerSupply Procedures Manual 060914 000 Rev C...

Page 2: ......

Page 3: ...Procedures Manual for Optiworx HWX Integrated Fan Power Supply HW PSFAN 1 110 HW PSFAN 2 110 HW PSFAN 1 220...

Page 4: ...P and SMART NETT are registered trade marks and Cable Network Manager CNM COR Convergence COR Connect FlexNode lumaCOR naviCOR Transfer Linearization and TL Technology are trademarks of C COR net Corp...

Page 5: ...week on the C COR net Technical Support Hotline Technical Support Hotline 888 827 2267 Or call C COR net worldwide headquarters Monday through Friday 8 AM to 5 PM ET 5GMT and ask for the Applications...

Page 6: ...bel Road State College PA 16801 7580 USA Providing Feedback on this Publication C COR net welcomes your suggestions and assistance in identifying any errors inaccuracies or misleading information Plea...

Page 7: ...be useful to users of this one Title Description Part Number HWX Equipment Shelf and Power Supply Controller Installation and 060674 001 User Instruction Manual Contains information required for inst...

Page 8: ...rostatic Discharge ESD protection practices Wear a grounded wrist strap when you touch a unit and when working on a unit always place it on an approved electrically grounded antistatic mat FCC Complia...

Page 9: ...CTION 1 DESCRIPTION 1 GENERAL DESCRIPTION 1 1 2 PHYSICAL DESCRIPTION 1 1 3 FUNCTIONAL DESCRIPTION 1 3 4 SPECIFICATIONS 1 4 SECTION 2 INSTALLATION 1 GENERAL 2 1 2 HOW TO USE THIS SECTION 2 1 3 SAFETY I...

Page 10: ...x FRONT MATTER 060914 000 Rev C This page deliberately blank...

Page 11: ...8 VDC outputs are compatible with telco standard A BATT B BATT DC inputs Each Integrated Fan Power Supply s DC output provides 48 VDC at 300 watts Warning The Integrated Fan Power Supply dual output a...

Page 12: ...anel Features LED AC Green when AC A and or B input is normal green 110 VAC version 90 130 VAC 220 VAC version 180 246VAC LED DC Green when DC A and or B output is normal green 48VDC 5 Rear Panel Feat...

Page 13: ...vides input and output status signals to the front panel LEDs The green AC LEDs will illuminate when the AC input to the converters are at an acceptable level The green DC LEDs will illuminate when th...

Page 14: ...PSFAN 2 110 25 15lb HW PSFAN 1 220 21 80lb Environmental Temperature Operating 0 C to 50 C 32 F to 122 F Storage 40 Cto 80 C 40 Fto 176 F Relative Humidity Operating 10 to 90 non condensing Storage 1...

Page 15: ...nstructions for installing the HWX Integrated Fan Power Supply proceed as follows 1 Find the task to be performed in the Installation Task Index List IXL 001 2 Locate the procedure for the task Each p...

Page 16: ...sembly and initial turn up and test Warning To prevent electrical shock never install electrical equipment in a wet location or during a lightning storm Caution HWX equipment is electrostatic discharg...

Page 17: ...low Then Go To Pg INSTALL INTEGRATED FAN POWER SUPPLY NTP 002 2 4 Unpack Equipment and Inspect for Damage DLP 500 2 6 Installing the HWX Integrated Fan Power Supply DLP 501 2 7 Integrated Fan Power Su...

Page 18: ...urces for one 1 HWX Equipment Shelf DO NOT attempt to connect this power supply to more than one equipment shelf Do Items Below in the Order Listed For Details Go To Pg DLP 500 2 6 DLP 501 2 7 DLP 502...

Page 19: ...res for an Integrated Fan Power Supply assembly HW PSFAN x xxx consists of performing the following item Do Items Below in the Order Listed For Details Go To Pg 1 Connect and turn on AC power to the a...

Page 20: ...s dents punctures etc that could indicate possible shipping damage If shipping damage is found refer to Contacting C COR net Technical Support on page v of this document for further instructions on ho...

Page 21: ...nt electrical shock never install electrical equipment in a wet location or during a lightning storm Caution The dual supply version of the Integrated Fan Power Supply HW PSFAN 2 110 is designed to pr...

Page 22: ...ets as required see Figure 501 1 and reattach them to the shelf in the new orientation reusing the original attaching screws Figure 501 1 Orienting Mounting Brackets For Integrated Fan Power Supply Mo...

Page 23: ...o Rear Support Brackets 4 For front mounting only Position the rear support mounting brackets right and left on the rear rack frame in a manner that both provides side and rear support to the Fan Powe...

Page 24: ...HWX Equipment Shelf if front mount place the bottom of the unit on the previously mounted rear support brackets step 4 Align the mounting holes in the ears with the applicable holes in the rack or ca...

Page 25: ...river to match terminal block screws Ground wire 16AWG minimum stranded conductor length as required DC power wire 18 AWG minimum stranded conductor length as required Insulated fork spade crimp termi...

Page 26: ...t supply HW PSFAN 1 xxx continue to step 6 If a redundant output supply HW PSFAN 2 110 go to step 7 6 Connect the Fan Power Supply terminal block Power Supply A 48V to either HWX Equipment Shelf s rea...

Page 27: ...an Power Supply s V screw terminal to the HWX Equipment Shelf s screw terminal tighten screw terminal securely b Connect the second wire from the Fan Power Supply s V screw terminal to the HWX Equipme...

Page 28: ...Fan Power Supply always follow Electrostatic Discharge ESD protection practices Wear a grounded wrist strap when you touch a unit Use antistatic packaging when transporting or storing units When worki...

Page 29: ...ails all the LED indicators will be extinguished Go to step 4 2 Are the AC LEDs green and the DC LEDs extinguished If Yes go to step 3 If No continue to step 4 3 Using the digital voltmeter observing...

Page 30: ...AC power module check that the AC power cord is connected to the IEC AC adapter and the male end of the power cord is connected to an active AC outlet If Yes continue to step 7 If No connect AC power...

Page 31: ...type When complete repeat DLP 503 Note If application of power to the fan assembly continues to blow fuses suspect faulty Fan Power Supply assembly Disconnect wiring to the shelf remove and return the...

Page 32: ...iangular symbol on the top of the fuse holder is pointing to the white line located at the bottom left side of the AC input power module as shown in the illustration For 220 VAC Model HW PSFAN 1 220 r...

Page 33: ...is not present on DC A but is present on DC B suspect defective power supply A Although the assembly can still be used to power the HWX Equipment Shelf the redundancy feature no longer exists The unit...

Page 34: ...PN 060914 000 Revision C October 2001 Page 2 20 2001 C COR net Corporation This page deliberately blank...

Page 35: ......

Page 36: ...6 5364255 Canadian Office 981 Mountview Court Oshawa Ontario L1K 2M1 Canada Tel 905 427 0366 Fax 905 428 0927 800 427 2559 Toll free for Canadian call only World Headquarters 60 Decibel Road State Col...

Reviews: