14
Advanced options
Under turn off state, press the key
to access advanced setting. Modify the parameter by using
the keys and and press the key
to confi rm and jump to the next parameter. When the
parameters are set, wait 5 seconds and the thermostat exit from the advanced setting menu.
Symbol
Description
Parameter setting
Default
value
A1
Measured
temperature
adjustment
-9-+9 ºC
0.0 ºC
A2
Temperature
hysteresis
0.5-2.5 ºC
1 ºC
A3
Not apply
Not apply
A4
Options of
sensor control
N1: Built-in sensor
N2 and N3: external sensor (Not apply to this
model)
N1
A5
Lock function
0: Half lock
1: Full lock
0
A6
High measured
temperature
value
1. 35 ºC-70 ºC
2. Under 35ºC, screen displays
and high
temperature limit is cancelled.
45 ºC
A7
Low measured
temperature
value
1. 1 ºC-10 ºC
2. Exceed 10ºC, screen displays
and low tem-
perature limit is cancelled.
5 ºC
A8
Low setting
temperature
value
1-10 ºC
5 ºC
A9
High setting
temperature
value
20-70 ºC
35 ºC
AA
Descaling
function
0: descaling function disabled;
1: descaling function enabled;
Descaling function: when valve is continuously
closed over 100 hours, it will be opened for 3
minutes automatically.
0
AB
Not apply
Not apply
AC
Weekly
programming
selection
0: 5+2
1: 6+1
2: 7
0
AA
Restore to
Factory default
setting
Hold down the key when this parameter is
displayed.
Note:
If when the thermostat is turn on, the symbols “E1” or “E2” are displayed, it is because a inco-
rrect setting of the parameter A4. Please, enter into the advanced option menu and select N1 for that
parameter.