Omron FINS Protocol – PLC Error Code Table (cont’d)
PLC Error Codes for Omron FINS
Panel Error Code
P499 Hex Value
Description
0x2507
Unit Error: I/O bus error.
0x2509
Unit Error: SYSMAC BUS/2 error.
0x250A
Unit Error: CPU Bus Unit Error.
0x250D
Unit Error: SYSMAC BUS No. duplication.
0x250F
Unit Error: Memory Error.
0x2510
Unit Error: SYSMAC BUS terminator missing.
0x2601
Command Error: No protection.
0x2602
Command Error: Incorrect password.
0x2604
Command Error: Protected.
0x2605
Command Error: Service already executing.
0x2606
Command Error: Service stopped.
0x2607
Command Error: No execution right.
0x2608
Command Error: Settings not complete.
0x2609
Command Error: Necessary items not set.
0x260A
Command Error: Number already defined.
0x260B
Command Error: Error will not clear.
0x3001
Access Right Error: No access right.
0x4001
Abort: Service aborted.
EA1-TCL-M Hardware User Manual, 1st Ed., 12/09
A
Appendix A: Panel & PLC Error Code Tables