background image

2  

 

Installation 

BS4662 square 

back box 

DIN standard round 

back box 

To switch from more than one position simply wire two or more units in parallel to achieve two way and intermediate 

switching. 
The detector should be sited so that the occupants of the room fall inside the detection pattern shown overleaf, at a 

recommended height of 2.8m for ceiling mounted sensors. Note that the higher the sensor is installed the shorter the 

detection range will be.  

 

Do not site within 1m of any lighting or ventilation equipment. 

 

Do not fix to a vibrating surface. 

 

Site as far away as possible from the surface of metal objects. 

Back box Compatibility 

Mounting 

The MWS1A-C is designed to fit both UK and EU style 
backboxes. 

Wiring 

25mm 

Do not over tighten 

Mounting screw cover 

MWS1A-C-PRM 

MWS1A-C-PRM-VFC 

MWS1A-C-PRM-LV 

L/OUT 

Neutral  

Circuit protection 

(if required) 

Load 

Neutral  

Live out 

Live 

NC 

NC 

NO 

COM 

NO 

Neutral  

Circuit protection 

(if required) 

NC 

NO 

Live 

Fault finding 

What if the load does not turn ON? 

 

Check to see if the live supply to the circuit is good. For the MWS1A-C-PRM version only: strap across the 

and 

LIVE OUT 

terminal to turn the load on. 

 

If the supply and wiring are good, check the LUX level setting. Increase the LUX level setting to allow the 
controller to turn on at higher ambient natural light level. 

 

What if the load does not turn OFF? 

 

Ensure that the area is left unoccupied for a greater time period than the time out period set using the switch. 

 

Make sure that the sensor is not adjacent to vibrating surfaces or objects (e.g. ventilation equipment).  

 

The unit may pick up movement through thin partitions or ceilings. Reduce the sensitivity. 

NC 

COM 

NO 