2
Installation
BS4662 square
back box
DIN standard round
back box
To switch from more than one position simply wire two or more units in parallel to achieve two way and intermediate
switching.
The detector should be sited so that the occupants of the room fall inside the detection pattern shown overleaf, at a
recommended height of 2.8m for ceiling mounted sensors. Note that the higher the sensor is installed the shorter the
detection range will be.
Do not site within 1m of any lighting or ventilation equipment.
Do not fix to a vibrating surface.
Site as far away as possible from the surface of metal objects.
Back box Compatibility
Mounting
The MWS1A-C is designed to fit both UK and EU style
backboxes.
Wiring
25mm
Do not over tighten
Mounting screw cover
MWS1A-C-PRM
MWS1A-C-PRM-VFC
MWS1A-C-PRM-LV
N
N
L/OUT
L
Neutral
Circuit protection
(if required)
Load
Neutral
Live out
Live
-
+
NC
-
NC
NO
COM
NO
+
Neutral
Circuit protection
(if required)
NC
NO
Live
Fault finding
What if the load does not turn ON?
Check to see if the live supply to the circuit is good. For the MWS1A-C-PRM version only: strap across the
L
and
LIVE OUT
terminal to turn the load on.
If the supply and wiring are good, check the LUX level setting. Increase the LUX level setting to allow the
controller to turn on at higher ambient natural light level.
What if the load does not turn OFF?
Ensure that the area is left unoccupied for a greater time period than the time out period set using the switch.
Make sure that the sensor is not adjacent to vibrating surfaces or objects (e.g. ventilation equipment).
The unit may pick up movement through thin partitions or ceilings. Reduce the sensitivity.
N
L
NC
COM
NO