Programming 

Parameter 
Name 

Default 
Value 

0

 

1

 

2

 

3

 

UHS5 Handset Graphics 

Description 

 

 

Button Activation 

 

 

On / Raise 

 

On 

 

 

 

 

Turn lights on. 

Off / Lower 

 

Off 

 

 

 

 

Turn lights off. 

Walk test 

Off 

On 

Off 

 

 

 

When set to On this causes a red LED to 
flash on the sensor when it detects 
movement. Use this feature to check for 
adequate sensitivity levels. 

Time Out 

(Time 
adjustment) 

10 mins 

1, 10 & 
20 
minutes 

5, 15 & 
30 
minutes 

 

 

 

Once the detector is turned on, this value 
sets how long the lights will stay on once 
movement has ceased. 

Lux on level 

(Switch 
level on) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to prevent the luminaires 
being switched on if the ambient light level 
is sufficient (adjustable between 1  
and 9). The luminaires will always be 
switched on at level 9.  

Lux off level 

(Switch 
level off) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to switch the luminaires off 
during occupancy if the ambient light level 
goes above the setting (adjustable between 
1 and 9). Level 9 will always keep the lights 
on. This setting can be used for “window 
row switching”.  

Sensitivity 

1, 5 & 9 

3, 6 & 8 

 

 

 

Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red 
and blue signified by the ‘Shift 1’ and ‘Shift 
2’ LEDs 

Number of Shift key presses 

The functionality of the MWS1A-C is controlled by a number of parameters which can be 
changed or programmed by any of the following devices: 

 

UHS5

 Infrared Handset. See below for programmable functions. 

 

UN-LCDHS 

Infrared Handset (with LCD). See user guide for full programming details. 

For most basic programming operations the UHS5 handset can be used and the following 
procedures are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit 
as shown below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED 
responses. 

Note: other functions on the UHS5 which are not shown below are not applicable to this 
product.

 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 