background image

POWER SUPPLY SPECIFICATION

Mains supply voltage / Rated current / VA:

230 Vac, 50/60 Hz / 1.35 A / 310 VA

Max. continuous output current (including charging):

5 A

Battery charge capacity:

7 Ah to 18 Ah

Max VRLA battery size/type determined by cabinet size:

BF360 range = up to 3 Ah (Note: BF360-12 without STU plate = 7 Ah)

(various models listed)

BF361 range = 7 Ah
BF362 range = up to 18 Ah

Power rating:

I max a = 4.6 A or 4.0 A (if PLK2 link fitted)
I max b = 5 A, charging turned off via CONN4 short

I min = 12 mA approx.

Maximum internal battery resistance:

Ri max = 600 mohm

Maximum output voltage:

V max = 30 V

Minimum output voltage at battery cut off:

V min = 19.2 V

Output ripple voltage (peak-to-peak):

450 mV @ 30 MHz bandwidth, 350 mV with a 100 nF loading.

Mains supply/battery charger monitored for failure:

YES

Batteries monitored for disconnection and failure:

YES

FUSES

Mains supply fuse (F1):

2 A HRC, 20 mm ceramic

Battery fuse (F2):

5 A F, 20 mm glass

POWER SUPPLY PCB CONNECTIONS

Mains Input (CONN1):

Three Mains supply input terminals: Live, Neutral & Earth

Fault Relay (CONN3):

Isolated relay output rated 1 A @ 50 V

Charge Off Input (CONN4):

Disablement of the battery charge, enabling the charge current to be used at the output during heavy load 
periods, volt-free short to 0 V to disable charger. Maximum cable length = 2.5 m.

Supply Output (CONN5):

24 Vdc output for auxiliary equipment at PSU’s rated output of 5 A

Battery Input (CONN5):

Connection to the VRLA batteries

PL1:

4-way connector for wiring loom from PCB to a display card, or OEM equipment, for transmission of C-TEC data protocol.

PL2:

High Temperature Output. Operates at approx. 55 

o

C internal box temperature, 30 V, 200 mA max. current sink.

PLK1:

‘Battery Monitoring’ link. Fit link if batteries NOT used.

PLK2:

‘Battery Charge Current’ link.

Fitted for 7 Ah to 18 Ah (1 A charge).

Note

: Special requests can be catered for, up to 60% of the total PSU output.

INDICATORS

Panel indicators (LEDs):

SUPPLY PRESENT (Green) – Indicates the supply is present at the output.
GENERAL FAULT (Amber) – Indicates a fault is present on the PSU. Call the engineer.
AUXILIARY FAULT (Amber) – Indicates a fault with an auxiliary unit (user-definable). 19 to 30 V, 3.5 to 6 mA.

Power Supply PCB (LED):

Hazardous Voltages Present (Red)

PHYSICAL ATTRIBUTES

Dimensions:

404 mm (width) x 404 mm (height) x 110 mm (depth)

Weight / Construction:

5.25 Kg (without batteries) / Metal lid and base

Enclosure finish:

RAL7035 textured

ACCESSORY PACK

1 x Instructions – Document No. DFU0003611 (this document); 1 x Allen key (for unfastening/securing the panel’s lid); 1 x 2 A HRC, 20 mm ceramic
fuse (spare Mains supply fuse F1); 1 x 5 A F, 20 mm glass fuse (spare battery fuse F2); 1 x set of links for PLK1 & PLK2; 1 x battery connection kit.

OPERATING CONDITIONS

The power supply enclosures have an IP30 rating (to EN60529:1992) and are designed for indoor use only. The components are selected to operate
within their specification when the environmental conditions outside the enclosure comply with class 3k5 of the latest edition of IEC 721-3-3:1978.
Temperature range: -5 

o

C to +40 

o

C. Maximum relative humidity: 95%.

CERTIFICATION

VdS Approval No.: G209197

CE Cert. No.: 0786-CPD-20892

FIRE ALARM

ancillaries

2 of 2

Approved Document No. DFU0003611 Rev 5

Batteries

CAUTION: There is a risk of explosion if incorrect batteries
are  used.  Always  dispose  of  used  batteries  in  accordance
with the battery manufacturers instructions.

For  the  emergency  standby  power  supply,  only  use  good
quality sealed VRLA batteries. Position and connect 2 x 12 V
batteries, as shown in diagram (see right).

Note:

On  a  standard  ‘as-supplied’  unit,  PLK1  (‘Battery

Monitoring’ link) is NOT fitted and a fault will occur on initial
power-up if fully charged batteries are NOT connected.

+ –

12 V BATTERY

+ –

12 V BATTERY

POWER SUPPLY 
          PCB 

3 x battery connection
leads (supplied with
accessories)

LOCATION OF 2 x 12 V BATTERIES AND CONNECTION
OF BATTERY LEADS TO POWER SUPPLY PCB

Black-  Red+

Output

CONN5

0V

+V

Battery

TECHNICAL SPECIFICATION

E&OE. No responsibility can be accepted by the manufacturer or distributors of these power supplies for any misinterpretation of this instruction,
or for the compliance of the system as a whole. The manufacturers policy is one of continuous improvement and we reserve the right to make
changes to product specifications at our discretion and without prior notice.

Manufacturer: Computionics Limited (C-TEC), Stephens Way, Wigan, Lancashire WN3 6PH, England - C-TEC.co.uk
Niederlassung Deutschland: C-TEC Germany Limited, Virchowstr. 32, D-33332 G

ϋ

tersloh -C-TEC-Germany.de

Reviews: