CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL 

 

 

Page 4 of 16 

 Commissioning/Programming Quick Start Guide 

 Approved Document No. DFU5020010 Rev 4 

 

 

 
 
 

1  Commissioning/Programming Overview 

 

This quick start commissioning/programming guide for the CAST XFP 16 and 32 zone panels details a 
procedure  for  creating  a  named,  zoned, 

‘one  out,  all  out’  fire  alarm  system  and  is  summarised  in 

sequential order below: 

 

 

Commission the panel by carrying out an auto address or loop learn. 

 

Install the XFP Programming Tools and connect the PC laptop to the panel. 

 

Load the auto address or loop learn data from the panel to the PC laptop. 

 

Name the loop devices. 

 

Name the Zones and assign loop devices to Zones/Groups/Sets. 

 

Edit the Group configuration. 

 

Enter the site details. 

 

Save 

the ‘config data file’ from the PC laptop to the panel. 

 

Note:

 Further custom configuration is possible using the XFP Programming tools but is beyond the 

scope of this quick start guide. 

 

2  Pre-Commissioning Checks at the Panel 

 
Before commissioning, ensure the following checks have been carried out at the panel. 
 

 

Check the continuity on the negative (-ve) line of the device loop(s) to ensure they are fault free. 

Note:

 Loop isolators are in the positive (+ve) line, therefore continuity cannot be tested. 

 

Connect all loop wiring to the panel (either 1 or 2 loops dependent on CAST XFP model). 

 

Connect mains and standby battery supplies to the panel. 

 

Upo

n  powering  up,  the  panel’s  display  will  show  a  number  of  start-up  messages  detailing, 

time/date, panel protocol, any faults, etc. 

 

Investigate and rectify 

any faults reported on the panel’s display. 

 

After all faults have been cleared, proceed to commission the panel. 

 

 

 

IMPORTANT NOTE 

THIS QUICK START GUIDE IS FOR AUTHORISED SYSTEM ENGINEERS FAMILIAR 
WITH ANALOGUE FIRE ALARM SYSTEMS AND FIRE ALARM STANDARDS. 
ENSURE  YOU  HAVE  ATTENDED  C-

TEC’S  AUTHORISED  TRAINING  COURSE 

BEFORE USING THE XFP PROGRAMMING TOOLS (PART NO. XFP507). 
 
IF YOU ARE IN  ANY DOUBT WHATSOEVER ABOUT  ANY DETAILS PROVIDED IN 
THIS QUICK START GUIDE, REFER TO THE CAST XFP ENGINEERING MANUALS 
(DFU5010000 

– 16 ZONE PANEL & DFU5010020 – 32 ZONE PANEL). 

Summary of Contents for CAST XFP

Page 1: ...le Fire Alarm Control Panel 1 Loop 16 Zone Panel Part No XFP501E CA 1 Loop 32 Zone Panel Part No XFP501 CA 2 Loop 32 Zone Panel Part No XFP502 CA Commissioning Programming Quick Start Guide Approved D...

Page 2: ...CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL Page 2 of 16 Commissioning Programming Quick Start Guide Approved Document No DFU5020010 Rev 4 FIG 1 CAST XFP Menu Structure...

Page 3: ...to Zones Groups Sets 11 4 7 Edit Group Configuration 14 4 8 Enter Site Details 15 4 9 Save Data from the PC Laptop to the Panel 16 E OE No responsibility can be accepted by the manufacturer or distrib...

Page 4: ...mmissioning Checks at the Panel Before commissioning ensure the following checks have been carried out at the panel Check the continuity on the negative ve line of the device loop s to ensure they are...

Page 5: ...t appears press the Accept button to continue Press the scroll button to select Yes then press the Accept button shown below When requested by the panel fit the NVM link shown below You now have two o...

Page 6: ...en press the Accept button shown below The panel will perform an auto address Wait for the process to complete and a brief summary window will appear similar to the one shown below Press the Accept bu...

Page 7: ...evious loop learn or PC upload you will be asked if you want to erase this information before the loop learn begins You now have two options Erase Loop 1 device data first No or Erase Loop 1 device da...

Page 8: ...ress the scroll button to select Yes then press the Accept button shown below The following message will appear Only if you are confident to proceed press the scroll button to select Yes then press th...

Page 9: ...the PC laptop to the RS232 port on the CAST XFP panel Note Application Note 0001 0 details setting up a Serial Comms Port on a PC laptop to connect to C TEC control panels App Note 001 00 is availabl...

Page 10: ...IG 2 shows the typical results after the auto address or loop learn data has been loaded from a CAST XFP panel into the XFP Programming Tools The tools have automatically allocated loop addresses and...

Page 11: ...ses and may also be a fire compartment To make the system understandable to the user you should name all the Zones The following example uses the Zone Config tab option to show the results of editing...

Page 12: ...s fire fault etc to the fire alarm panel e g smoke heat detectors MCPs and the input channels of I O units Click on the Loop Summary tab to open the Loop Summary window For each input device click on...

Page 13: ...sign a device to a Group see FIG 5 Note In order to make any changes to the Zone Group Set data in the Loop Summary window click on the Enable Type Zone Changes box There are a maximum of 16 Groups wh...

Page 14: ...ps 6 to 16 are not configured There are two conventional sounders circuits in the CAST XFP panel i e Panel Sounder 1 Panel Sounder 2 By default Panel Sounder 1 assigns to Group 1 and Panel Sounder 2 a...

Page 15: ...e text shown on the panel s display when the Maintenance Date is reached By default Service Required Call Engineer is entered Typically set the maintenance date to 12 months after the commissioning da...

Page 16: ...fig data file from the PC laptop to the panel by clicking on the toolbar icon shown right When requested by the panel fit the NVM link shown below The following message will appear at the panel Wait f...

Reviews: