CAST XFP ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Commissioning/Programming Quick Start Guide
Approved Document No. DFU5020010 Rev 4
Page 7 of 16
3.2 Loop Learn
NB! LOOP LEARN WILL NOT AUTO ADDRESS DEVICES.
Loop learn requires all devices to be pre-addressed, e.g. using the CAPROG handheld
programmer
.
New addresses will not be assigned.
During a loop learn, the panel interrogates every pre-addressed device on the loop to see if an addressable
unit is present and, if so, find out what type of device it is.
At the panel, enter
AL3 (4444) > Commissioning Functions > Loop Learn.
When the LOOP LEARN prompt appears, press the Accept
button to continue.
Press the scroll
▲
button to select ‘Yes’ then press the Accept
button shown below:
When requested by the panel fit the NVM link shown below:
As the panel may already have loop device data stored in its memory from a previous loop learn or PC
upload, you will be asked if you want to erase this information before the loop learn begins.
You now have two options,
‘Erase Loop 1 device data first? No’, or ‘Erase Loop 1 device data first? Yes’, as
detailed below:
Option 1: Select ‘Erase Loop 1 device data first? No’
Use this option if you do not want to erase the stored loop device data. The panel will learn the loop without
overwriting existing data, e.g. zone and group allocation, device names, etc., which will remain unchanged.
The only data that will be overwritten is device type and whether or not it is fitted.
Press the scroll
▲
button to select ‘No’ then press the Accept
button shown below:
The panel will start a loop learn. Wait for the process to complete and a summary window will appear, similar
to the one shown below:
Press the Accept
button then press Escape
button x 3 to return the panel to a normal condition.
When requested by the panel remove the NVM link shown below:
112 devices found
Auto learn complete, Press Accept
Please fit the NVM Link now
or press ESCape to abort