05/09/16

Attestation of Conformity to ATEX 2014/34/UE Directive

Inserted in the following document: M19/e general instructions (leaflet inserted in every package)

Terminal blocks approved in conformity to ATEX 2014/34/UE Directive
Terminal blocks “at increased safety” (Ex e) are manufactured according to IEC/EN 60079-0,
IEC/EN 60079-7 Std. and bear, on the insulating body, the name of the product and the electrical
characteristics.

ATEX Marking:

0722

I

M 2 Ex eb

I

Mb

II

2G Ex eb

II

C

Gb

0722

= number of Notifying Body (CESI) for the ATEX surveillance

I

M2

= group

I

(mines), category

M2

II

2 G

= group

II

(surface) category

2 G

(gas)

Ex eb

= “increased safety” protection mode

II

C

= gas group

Gb

= EPL

I

= group

I

(mines)

Mb

= EPL

V

= rated voltage

The CE Marking indicates the Conformity to EU Low-voltage Directive 2014/35/UE
Terminal blocks must be installed in enclosures “at increased safety”; the enclosure / terminal blocks
assembly must be subjected to separate certification

Carlo Zaccone
Legale Rappresentante

Summary of Contents for DBC.4

Page 1: ...ining terminal blocks and by END BRACKETS that are located at the ends of the assembly in a way to obtain a compact and single arrangement As the back of each terminal block performs the function of insulating wall for the adjoining terminal block an END SECTION is necessary to close and provide appropriate insulation to the first terminal block forming the assembly Rail assemblies can be subdivid...

Page 2: ...l skipping Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac DBC 4 upper level 250 250 250 250 250 DBC 4 lower level 250 250 250 250 250 Notes rated voltage values can be subjected to a 10 tolerance as listed in Table 1 of IEC 60079 7 Std TERMINAL BLOCK JUMPER MULTIPLE COMMONING BAR SCREW AND SLEEVE CURRENT OF THE JUMPER A DBC 4 PTC ...

Page 3: ...ks to their coupling it is possible to apply the correct contact pressure By acting on the tightening screw the collar tightens the conductor against the conducting body which is manufactured in tin plated copper With the clamping yoke tightening system a gas proof particularly safe connection is guaranteed Thanks to the force applied during the tightening process the overlapped threaded parts sys...

Page 4: ...body the name of the product and the electrical characteristics ATEX Marking 0722 I M 2 Ex eb I Mb II 2G Ex eb IIC Gb 0722 number of Notifying Body CESI for the ATEX surveillance I M2 group I mines category M2 II 2 G group II surface category 2 G gas Ex eb increased safety protection mode IIC gas group Gb EPL I group I mines Mb EPL V rated voltage The CE Marking indicates the Conformity to EU Low ...

Reviews: