background image

19

6. Lubricate the end of the pipe and thread of the flare

connection with refrigerant oil. Tighten by hand and then

use two wrenches (see Fig. 39) to tighten all connections.

Adjustable wrench or torque wrench

Outdoor end
Indoor end

3

1

2

A07201

Fig. 39 – Tightening Connections

START--UP

PRELIMINARY CHECKS

1. Check condensate drainage system; on the opposite side of

the drain connection, insert a water bottle up into the fan
coil unit and fill the drain pan. Water must flow steadily; if
not, check the pipe slope or inspect for any pipe restrictions.

2. Make sure all wiring connections are correct and they are

tight.

3. Field electrical power source must agree with unit name

plate rating.

4. Check that all barriers, covers, and panels are in place.

Ensure that the filters and return--air grilles on the indoor
unit have been installed and that the discharge louvers are

positioned correctly.

5. All service valves must be closed.
6. On units with crankcase heaters, ensure belly--band heaters

are tight around the compressor.

EVACUATE AND DEHYDRATE THE

SYSTEM

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Never use the system compressor as a vacuum pump.

Using Vacuum Pump

1. Completely tighten flare nuts A, B, C, D, connect manifold

gage charge hose to a charge port of the low side service

valve (see Fig. 40).

2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 41).
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation

method.

6. After evacuation is complete, fully close the low side of

manifold gage and stop operation of vacuum pump.

7. The factory charge contained in the outdoor unit is good for up

to 25 ft. (8 m) of line length. For refrigerant lines longer than

25 ft. (8 m), add charge up to the maximum allowable length
as specified in the residential Long Line Application Guide.

8. Disconnect charge hose from charge connection of the low

side service valve.

9. Fully open service valves B and A.

10. Securely tighten caps of service valves.

Outdoor Unit

Indoor Unit

Refrigerant

Service Valve

Low Side

High Side

A

B

C

D

A07360

Fig. 40 – Service Valve

Manifold Gage

500 microns

Low side valve

High side valve

Charge hose

Charge hose

Vacuum pump

Low side valve

A07361

Fig. 41 – Manifold

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and

liquid water (see Fig. 42).

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS

2500

3000

3500

4000

4500

5000

A95424

Fig. 42 – Deep Vacuum Graph

Summary of Contents for 40MKCB**F/24AHA4

Page 1: ...aller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Page 2: ...Only 018 24AHA418A003 124ANS018000 40MKCB18F 3 024 24AHA424A003 124ANS024000 40MKCB34F 3 030 24AHA430A003 124ANS030000 40MKCB34F 3 034 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 054 24AHA448A003 5 6 12...

Page 3: ...ONS INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor Indoor Unit Size BTU Hr Height H in mm Width W in mm Depth D in mm Operat...

Page 4: ...4 DIMENSIONS OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48 24 x 50...

Page 5: ...NS030000 124ANS036000 124ANS048000 Table 7 Dimensions SI ACs 124ANS018000 124ANS024000 124ANS030000 124ANS036000 124ANS048000 Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Di...

Page 6: ...nstalling single or multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow...

Page 7: ...g cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code fo...

Page 8: ...stall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Whe...

Page 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Page 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Page 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Page 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Page 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Page 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting diagram A150282 Fig 29...

Page 15: ...0 208 230 3 253 197 71 9 3 1 2 12 8 20 48 50 83 1 13 7 1 45 18 6 30 36 60 460 3 506 414 38 5 6 0 6 7 6 15 48 60 41 6 2 0 8 8 6 15 Table 19 40MKCB F Electrical Data Indoor Unit Size BTU Hr V Ph Hz Volt...

Page 16: ...r Live wire L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compress...

Page 17: ...LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Ver ticals wingmotor interface CN13 horizontalswingmotor interface CN10 Disp layboardinterface CN15 Sign alinterface Y...

Page 18: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Page 19: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 40 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 41 4 Start vacuum pump 5...

Page 20: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Page 21: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Page 22: ...s NO Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp Display digital tube 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Page 23: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Page 24: ...P D 7310 W Morris St D Indianapolis IN 46231 Edition Date 07 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC...

Reviews: