background image

20

Triple Evacuation Method

The triple evacuation method should only be used when vacuum

pump is only capable of pumping down to 28 in. of mercury

vacuum and system does not contain any liquid water. Refer to Fig.

43 and proceed as follows:

1. Pump system down to 28 in. of mercury and allow pump to

continue operating for an additional 15 minutes.

2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and

open until system pressure is 2 psig.

4. Close service valve and allow system to stand for 1 hr.

During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture.

5. Repeat this procedure as indicated in Fig. 43. System will

then be free of any contaminants and water vapor.

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

RELEASE CHARGE INTO SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

A95425

Fig. 43 – Triple Evacuation Method

TO START THE UNIT:

1. If the outdoor unit is equipped with a crankcase heater, turn

on the indoor and outdoor disconnect switches to supply

power to the system 6 hours before starting the system.

2. Release charge into the system by opening (back--seating)

liquid and suction line service valves.

3. Set the wireless remote control or wired remote control

below ambient temperature. Operate the unit for 15 minutes.

4. Refer to Table 12 to determine if additional charge is

required. Also, if you have a long line application, refer to

the Residential Long Line Application Guide to determine
the additional charge that is required beyond 25 ft (7.6 m).

5. Charge should be added as liquid (not gas) slowly and

carefully to low side to avoid liquid slugging.

6. Start unit with operation test. In test mode the unit will run

in cooling and heating (on heat pumps) regardless if there is
demand or not.

TEST OPERATION FOR UNDER

CEILING/CONSOLE

Perform test operation after completing gas leak and electrical

safety check (see Fig. 44).

1. Push the “ON/OFF” button on Remote Control to begin

testing.

NOTE

: A protection feature prevents air conditioner from being

activated for approximately 3 to 4 minutes.

2. Push MODE button, select COOLING, HEATING, FAN

mode to check if all functions work correctly.

3. To run the test using the manual button in the indoor unit:

S

Push the manual switch once to energize the unit.

The set conditions of manual operation are as follows:

· Preset set point: 76

_

F (24

_

C)

· Fan speed: AUTO
· Discharge air direction: Pre--set position based on

operation in “Cool” or “Heat” mode.

4. Be sure to set manual switch to “OFF” (by pushing it twice

again) after finishing test operation.

MANUAL

A150284

Fig. 44 – Manual Button from display board

Manual Operation

Manual operation can be accessed by pressing manual button on

display panel. Press the manual button repeatedly to change modes

as follows:

S

Once = AUTO mode [heat, cool or fan, 24

_

C and auto

fan speed.

S

Twice = COOLING mode [switch to AUTO mode after
30 minutes (mainly used for trial operation)]

S

Three times = OFF

NOTE

: For Heat Pumps, follow the same procedure.

Visually check that the condensate is being discharged from the

unit. If the unit is running in heating mode, the condensate needs to

be checked and the following needs to be performed:

S

Remove grille and frame from the unit.

S

On the opposite side of the drain connection, insert a

water bottle up into the fan coil unit and fill drain pan.
See Fig. 45.

A09552

Fig. 45 – Inserting Water Into Drain Pan

Water must flow regularly with condensate pump energized. If not,

check the pipe slope or see if there are any pipe restrictions.

NOTE

: The unit is equipped with a safety float switch to de--energize

the compressor if the drain pan water level gets too high.

Summary of Contents for 40MKCB**F/24AHA4

Page 1: ...aller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Page 2: ...Only 018 24AHA418A003 124ANS018000 40MKCB18F 3 024 24AHA424A003 124ANS024000 40MKCB34F 3 030 24AHA430A003 124ANS030000 40MKCB34F 3 034 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 054 24AHA448A003 5 6 12...

Page 3: ...ONS INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor Indoor Unit Size BTU Hr Height H in mm Width W in mm Depth D in mm Operat...

Page 4: ...4 DIMENSIONS OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48 24 x 50...

Page 5: ...NS030000 124ANS036000 124ANS048000 Table 7 Dimensions SI ACs 124ANS018000 124ANS024000 124ANS030000 124ANS036000 124ANS048000 Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Di...

Page 6: ...nstalling single or multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow...

Page 7: ...g cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code fo...

Page 8: ...stall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Whe...

Page 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Page 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Page 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Page 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Page 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Page 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting diagram A150282 Fig 29...

Page 15: ...0 208 230 3 253 197 71 9 3 1 2 12 8 20 48 50 83 1 13 7 1 45 18 6 30 36 60 460 3 506 414 38 5 6 0 6 7 6 15 48 60 41 6 2 0 8 8 6 15 Table 19 40MKCB F Electrical Data Indoor Unit Size BTU Hr V Ph Hz Volt...

Page 16: ...r Live wire L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compress...

Page 17: ...LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Ver ticals wingmotor interface CN13 horizontalswingmotor interface CN10 Disp layboardinterface CN15 Sign alinterface Y...

Page 18: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Page 19: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 40 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 41 4 Start vacuum pump 5...

Page 20: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Page 21: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Page 22: ...s NO Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp Display digital tube 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Page 23: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Page 24: ...P D 7310 W Morris St D Indianapolis IN 46231 Edition Date 07 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC...

Reviews: