background image

12

Table 6 – Piping Water Volumes

PIPE SIZE

COPPER PIPE FACTOR

STEEL PIPE FACTOR

1/2---IN.

82.5

63.5

3/4---IN.

40.0

36.0

1---IN.

23.3

22.2

1---1/4---IN.

15.3

12.8

1---1/2---IN.

10.8

9.5

2---IN.

6.2

5.8

---Divide total length of piping in feet by appropriate factor in table to de-

termine volume in gallons.

An air purger is used to remove air from system. It is installed in
supply line. It eliminates air from water before it reaches radiators

and bleeds off this air.

E. Main

Air

Vent

for

Downflow

Systems

or

Diaphragm--Type Expansion Tank (Not Provided)

Before a system is filled with water, there is air in pipes and

radiation units. Some of it will be trapped as system fills. It is
possible to eliminate most of this air through air vents on

radiation units. A main air vent speeds and simplifies this process.

It should be installed on highest point in supply main when all
radiation is below top of boiler.

F. Aquastat Relay Control (Provided)

The water temperature limit control in aquastat relay is adjustable

and may be set as necessary. It may be set as low as 140

_

F or as

high as 240

_

F. This depends on type and amount of radiation

involved and weather conditions.

G. Automatic Fill Valve (Not Provided)

For safe, efficient operation, a hot water system must be filled
with water. Adding new water when needed can be done

manually (by use of a hand valve in water supply line). This

requires regular attention to system’s needs. An automatic fill
valve accomplishes this without attention. It is installed in supply

line on hot water boilers only. The valve operates through water
pressure differentials. It does not require electrical connection.

H. Drain Valve (Provided)

This manual valve provides a means of draining all water from

boiler and system. It is installed in a tee where return line enters

boiler.

I. Circulating Pump (Provided)

Every forced hot water system requires a circulating pump. A
separate pump or zone valve is required for each zone if there are

2 or more zones. The circulator must have the capacity to provide
the circulation required by the heating system. The circulator

should be connected to the supply main and must be wired into

the boiler’s electrical system. See the prior pages of installation
section for piping configurations with the circulator located on

the supply main piping using zone circulators or zone valves.
When the piping is arranged with zone circulators and no bypass

piping, the circulator provided with the boiler may be used as a
zone circulator. Both piping arrangements allow the circulator to

pump away from the expansion tank and show how the piping

should be arranged to allow the heating system to be easily
purged of air.

J. Oil Solenoid Valve

The Beckett oil burner uses a standard solenoid valve. Upon

burner shutdown, a standard solenoid valve stops the flow of oil
to the nozzle. Without the solenoid valve, the oil pump continues

to pump oil to the burner nozzle until the motor winds down

below the pump cut--off speed. The Riello oil burner has a delay
oil solenoid valve. The delay solenoid valve provides the same

shut down action of the standard solenoid valve, plus on burner
start--up, the delay solenoid valve remains closed for an

additional 15 seconds. This allows the burner fan motor to

pre--purge the combustion chamber and the oil pump to bring the
supply oil pressure up to its set point helping to provide a clean

light off.

Filling Boiler

OPTION #1

A. How a Hot Water System Operates

The entire heating system (boiler, piping, and radiation units) is

filled with water. As water in boiler is heated, it is pumped from

top of boiler through supply main to radiation units. The cooler
water in them flows back through return main to boiler. This

provides positive and rapid response to thermostat.

B. Filling System With Water

a. Close the main shutoff valve, isolation valves, and

zone valves (if applicable). If bypass piping is

installed, also close the two throttling valves. Leave
the boiler service shutoff valve (if installed) and the
balancing valves to each heating zone fully open.

b. Open the following valves in order: the drain valve for

power purging, isolating valves before and after the

boiler circulator (if applicable), both throttling valves
(if applicable), and then open the fill line shutoff
valve. Water will fill the bypass piping and push air

through the piping and out the power purging drain
valve. When the power purging drain valve runs air

free, close the bypass throttling valve (leaving the
throttling valve to the supply piping fully open)

c. Next, open the isolation valve (or zone valve) to the

first zone. Water will fill the piping and push any air
out the power purging drain valve. When the power

purging drain valve runs air free, close the isolation
valve or zone valve. Repeat this procedure for the

remaining heating zones.

d. Once all of the zones are filled with water and purged

of air, close the power purging drain valve and fill line

shut off valve, open the main shutoff valve, and adjust
the throttling valves and balancing valves as required.

OPTION #2

1. Close air vents on all radiation units. Open valves to these

units.

2. Make sure boiler and expansion tank drain cocks are

closed. The air bleed screw on tank drain fitting should be

closed.

3. Open valve in line from boiler to expansion tank.
4. Open water inlet to boiler and leave it open.
5. Start with the LOWEST radiation unit. Open the air vent

on this radiation unit. When all air has escaped and water

starts to flow from vent, close air vent.

6. Proceed to next lowest radiation unit and repeat process

outlined in item 5. Repeat until every radiation unit in
system has been covered. End with the highest unit in
system.

If units have automatic vents, this manual venting is unnecessary
but will speed up proper filling of system.
If system is a closed expansion tank system, there should be an

automatic fill valve. It may be left open to refill system
automatically as needed.
Check temperature--pressure gage. Note position of hand
indicating pressure. This should be between 10 and 15 psi. Any

lowering of this movable hand below 10 psi indicates loss of
water due to leakage. The automatic fill valve should compensate

for this. If it does not, manually open this valve to refill system

BW

4

/BW

5

Summary of Contents for BW4

Page 1: ...hed to or shipped with unit and other safety precautions that may apply Recognize safety information This is the safety alert symbol When you see this symbol on unit or in instructions and manuals be alert to potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...by the boiler manufacturer and the expansion tank manufacturer 13 Expansion tank performance and life expectancy can be hindered by overfilling the boiler An initial fill pressure of 10 12 psig is recommended For higher fill pressures the expansion tank s air charge will need to be increased to match the fill pressure Consult the manufacturer s guidelines for sizing and selection 14 Purging the he...

Page 3: ... installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installer service agency fuel oil supplier or your distributor or branch for information or assistance The qualified installer or agency must use only factory authorized and list...

Page 4: ...ck with local authorities and obtain professional help where needed The Operation Instructions Final Checks and Adjustments and Maintenance sections in this manual are vital to the proper and safe operation of the heating system Take the time to be sure they are all done Locating the Boiler If boiler is part of a planned heating system locate it as close as possible to where it is shown on plan If...

Page 5: ... 6 8 460 N A BW4BAH210 BW4RAH210 4 126 111 97 0 90 86 0 8 X8 X15 17 3 4 6 9 5 8 533 N A 4 175 150 130 1 25 83 9 8 X8 X15 17 3 4 6 9 5 8 533 N A 4 210 178 155 1 50 82 4 8 X8 X15 17 3 4 6 9 5 8 533 N A BW4BAH280 BW4RAH280 5 168 147 128 1 20 86 5 8 X8 X15 21 6 11 1 2 620 N A 5 245 209 182 1 75 83 6 8 X8 X15 21 6 11 1 2 620 N A 5 280 236 205 2 00 82 0 8 X8 X20 21 6 11 1 2 620 N A Shaded areas are as s...

Page 6: ...CK OF OXYGEN WARNING UNIT LIFE REDUCTION HAZARD Failure to follow this warning could result in personal injury death and or property damage Air for combustion must not be contaminated by halogen compounds which include fluoride chloride bromide and iodide These elements are found in aerosol sprays detergents bleaches cleaning solvents salts air fresheners and other household products WARNING Enoug...

Page 7: ... a minimum free area of 1 sq in per 2000 Btuh of total input rating of all equipment in the enclosure 4 When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall not be less than 3 in Boilers With Tankless Heater Coil Boilers may be factory packaged with a tankless heater coil The u...

Page 8: ...th supply and return lines should be piped to the front section or both to the rear section The boiler should NOT be piped return line to the front supply line to the rear or vice versa as this will cause boiler water to short circuit heat exchanger The connections may require certain additional fittings and parts as shown on diagrams See Fig 9 10 and 11 If installing an entire new heating system ...

Page 9: ...LVE THROTTLING VALVE CIRCULATOR PUMP AQUASTAT S R MAIN SHUTOFF VALVE ADJUST THE TWO THROTTLINE VALVES TO MAINTAIN AT LEAST 120 O F IN THE BOILER RETURN THE THROTTLING VALVES ARE USED FOR BYPASS PIPING IF REQUIRED A01034 Fig 10 Bypass Piping Circulator on Supply FILTROL WITH AIR PURGER AUTOMATIC FILL VALVE SUPPLY TO SYSTEM SHUTOFF VALVE BOILER SERVICE FILL LINE WITH SHUT OFF VALVE RETURN FROM SYSTE...

Page 10: ... grounded ground rod C Electrical Power Supply ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Turn off electric power at fuse box before making any line voltage connections Follow local electric codes WARNING All electrical work must conform to local codes as well as the National Electrical Code If not familiar with wiring and codes in general have ...

Page 11: ...ype expansion tank a in the supply line with the circulator located after the expansion tank or b off the e3 4 in tapping provided on the top of the rear casting with the circulator mounted directly off the boiler s supply piping connection This configuration allows the circulator to pump away from the expansion tank for improved air elimination and system performance The air reliminator fitting o...

Page 12: ...e The delay solenoid valve provides the same shut down action of the standard solenoid valve plus on burner start up the delay solenoid valve remains closed for an additional 15 seconds This allows the burner fan motor to pre purge the combustion chamber and the oil pump to bring the supply oil pressure up to its set point helping to provide a clean light off Filling Boiler OPTION 1 A How a Hot Wa...

Page 13: ...vide air for combustion and operation of barometric draft control The room should be isolated from any area served by exhaust fans Do not install exhaust fans in this room See Fresh Air for Combustion section earlier in this document Draft Regulators Provided A draft regulator is required It should preferably be mounted in smoke pipe Use a draft gage to adjust to proper opening When burner air sup...

Page 14: ... PLATE WITNESS MARK BECKETT AFG VARIABLE V1 HEAD ADJUSTMENTS AND SETTINGS A06664 Fig 14 Beckett Burner Setting Variable V1 Head 5 32 GAP 7 16 ABOVE NOZZLE DIMENSION N SEE ABOVE BURNER F HEAD MODEL F0 THRU F31 DIMENSION N HEAD TO NOZZLE 1 16 BECKETT AFG BURNER ELECTRODE ADJUSTMENTS F HEADS A06665 Fig 15 Beckett Burner Setting Fixed F Head 140 210 A06506 Fig 16 Riello 40 F5 Burner Electrode Adjustme...

Page 15: ...kept clean and free of dirt lint and oil so as to maintain proper amount of air the fuel requires to burn NOTE If any component parts must be replaced always use parts recommended by burner manufacturer F Fan and Blower Housing Check burner blower wheel for dirt grease and grime Clean as necessary Check motor is attached to burner housing and wheel is attached tightly to motor shaft Check pump cou...

Page 16: ...n for some time recheck the whole system for leaks and recheck boiler and vent pipe for leaks Replace or patch any boiler seals that are faulty FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Never burn garbage or paper in the unit and never leave combustible material around it WARNING Relief Valve This valve should open automatically when system press...

Page 17: ...er and if applicable burner head 3 Remove the burner drawer assembly clean the electrodes and then reset the electrode spark gap per the manufacturer s recommendations 4 Replace the oil nozzle with the exact same size and type recommended for use on this boiler 5 Reinstall the burner drawer assembly making sure the head location and size if applicable are per the manufacturer s recommendations If ...

Page 18: ...ithout Tankless Coil AQUASTAT HIGH LIMIT CONTROLLER The aquastat control s high limit contacts open and turn off the burner when the boiler water temperature reaches the control s high limit set point The high limit contracts automatically reset after the boiler water temperature drops past the set point by 10_ F which is a fixed differential When the thermostat controls call for domestic space he...

Page 19: ...RING OIL BURNER MOTOR L8148A AQUASTAT IGN TRANS B W CIRCULATOR B W B W W B O B B R4184D RELAY Y Y CAD CEL IK1 JUMPER IK IK2 B2 C2 C1 ZC F F ZR B1 L2 T T T T G GND L1 HOT L2 L1 L2 B1 B2 C1 B R ZR B R W ZC C2 HIGH LIMIT 1K2 LOW LIMIT CIRCULATOR COLOR CODE BK BLACK O ORANGE Y YELLOW R RED W WHITE 1K1 1K A R LINE VOLTAGE CLASS II 24 VOLTS T T L2 L1 3 F F B 3 T T C1 C2 B2 B1 L2 L1 B R G B2 B1 C2 C1 COL...

Page 20: ...20 A06504 Fig 21 Boilers Without Tankless Coil and Honeywell L8148 Aquastat Control BW4 BW5 ...

Page 21: ...21 F5 only A06505 Fig 22 Boilers With Tankless Coil and Honeywell L8124C Aquastat Control and Riello Burners BW4 BW5 ...

Page 22: ...d or burner may be dirty Clean all flue passages and vent pipe Have burner cleaned and readjusted Burner may not be firing at proper rate Check nozzle size it there is any doubt Have burner adjusted Burner may be short cycling Short cycling too frequent off and on of burner causes sooting If boiler and or burner becomes Burner may be short cycling dirty at frequent intervals correct the dirt condi...

Page 23: ...ction 8 in X 12 in 4 section 8 in X 20 in 5 146 30 031 10 Collector Base 3 section 425 00 279 4 section 425 00 280 5 section 425 00 281 11 Tape Plym Collector insulation 1 in X 1 16 in X 100 Included in Part 425 00 279 80 81 12 Collector Top Included in part 425 00 279 80 81 13 Wing Nut 8 32 Brass 137 04 007 14 Screw 14 X 3 4 in HWH SL S M SC Hex Washer Head Slotted Sheet Metal Screw 146 95 109 15...

Page 24: ...chined 403 00 014 11 Washer Lock Plain 5 16 in 146 95 123 12 Bolt 5 16 in X 3 8 in Socket SH Shoulder BLT Bolt 1 4 in 20 TH Thread 146 95 122 Fig 24 Swing Fire Door Assembly Table 11 Beckett Oil Burner Service Parts OIL BURNER REPAIR PARTS BURNER NOT SHOWN PART NUMBER Burner Motor RP 015 00 Fuel Pump RP04501 Oil Solenoid Valve RP04601 Ignitor or Ignition Transformer RP02001 Oil Primary Control 718...

Page 25: ...4 3 XXX 4 XXX 2 1 5 1 6 4 7 21 9b 4 1 XXX A01042 Item Description 3 Section Part Number 4 Section Part Number 5 Section Part Number Complete Jacket 42670289AB 42670290AB 42670291AB 1 Panel Right Empire II 42570244AB 42570245AB 42570246AB 2 Jacket Panel Back 42570269AB 42570269AB 42570269AB 3 Jacket Panel Top 42570254AB 42570255AB 42570256AB 4 Panel Left Empire II 42570264AB 42570265AB 42570266AB 5...

Page 26: ... tankless coil 433 00 521 433 00 521 433 00 521 2b L8124C 1094 Aquastat Control with tankless coil 146 62 022 146 62 022 146 62 022 3a Taco 007 Circulator CI 001 03 CI 001 03 CI 001 03 3c Taco Circulator Gaskets 146 26 050 146 26 050 146 26 050 ____ 1 1 4 Flange set with gaskets nuts and bolts 146 26 049 146 26 049 146 26 049 4 Temperature Pressure Gauge 2 Stem 1260006 1260006 1260006 5a 1 1 4 x 2...

Reviews: