background image

16

Table 8 – Riello Oil Burner Specifications

BASE

MODEL

BOILER

INPUT (BTUH)

DELEVAN

OIL NOZZLE

FIRING

RATE (GPM)

TURBULATOR/AIR

SHUTTER SETTING

OIL PUMP PRESSURE

(PSIG)

OIL

BURNER

140

91,000

0.50--- 70ºW

0.65

0.5 / 2.0

155

F5

105,000

0.65--- 70ºW

0.75

2.0 / 2.2

150

F5

140,000

0.85--- 70ºW

1.00

2.0 / 3.2

170

F5

210

126,000

0.75--- 70ºW

0.9

1.5 / 2.6

160

F5

175,000

1.00--- 70ºW

1.25

2.5 / 3.8

170

F5

210,000

1.25--- 70ºW

1.5

4.0 / 7.0

175

F5

280

245,000

1.50--- 70ºW

1.75

2.0 / 3.8

155

F10

280,000

1.75--- 70ºW

2.00

2.5 / 4.1

155

F10

Note: All Riello 40 F5 and F10 oil burners are factory preset at 145 psig.

Checking and Adjusting Controls

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not attempt to start the burner when excess oil has

accumulated, when unit if full of vapor, or when the

combustion chamber is very hot.

!

WARNING

IMPORTANT

: These instructions must be followed carefully.

A. Adjusting Operating Controls

Instructions for each control are included. Refer to Table 8 for

recommended settings for the first adjustment:
These settings can be changed after gaining familiarity with how
system responds. If system does not give quite enough heat in

very cold weather, ,the high limit setting can be raised to 220

_

F.

If more domestic hot water is required, the low limit setting can

also be raised

B. Checking Thermostat Opeation

When set above temperature indicated on thermometer, boiler
burner should start. Make certain thermostat shuts boiler down

when room temperature reaches selected setting and starts boiler

operating when room temperature falls a few degrees.

NOTE

: Do not start burner unless all cleanout doors are secured

in place.

MAINTENANCE

To assure trouble--free operation, we recommend that flue
passages, burner, combustion chamber area (target wall and fire

door insulation), burner adjustment, operation of controls, and

boiler seals (door gasket or silicone seal, cast iron seals and flue
collector) be checked ONCE EACH YEAR by a competent

service technician.
BEFORE THE START OF EACH SEASON (or whenever

system has been shut down for some time), recheck the whole

system for leaks and recheck boiler and vent pipe for leaks.
Replace or patch any boiler seals that are faulty.

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury or death.
Never burn garbage or paper in the unit, and never leave

combustible material around it.

!

WARNING

Relief Valve

This valve should open automatically when system pressure

exceeds the safe limit (30 psi). Should it ever fail to open under
this condition, shut system down. Drain it until pressure is

reduced below safe limit, then have valve replaced immediately.
The relief valve should be tested monthly during heating season.

Prior to testing, make certain a discharge pipe is properly

connected to the valve outlet and arranged so as to contain and
safely dispose of boiler discharge. Hold the trip lever fully open

for at least five seconds in order to flush free any sediment that
may lodge on the valve seat. Then permit the valve to snap shut.

Conventional Expansion Tank

As previously noted, this tank may become waterlogged or may

receive an excess of air. Frequent automatic opening of relief
valve indicates waterlogging. A high boiler temperature

accompanied by unusually low radiation unit temperature (and

“knocking”) indicates excess air in tank. To correct either
condition, close valve between boiler and tank. Drain tank until it

is empty. Check all tank plugs and fittings. Tighten as necessary.
Open valve between boiler and tank. Water will rise to normal

height in tank if automatic fill valve is installed, otherwise,
manually refill system.

Diaphragm Expansion Tank

As previously noted, this tank may become waterlogged or may

receive an excess of air. Frequent automatic opening of relief
valve indicates waterlogging. A high boiler temperature

accompanied by unusually low radiation unit temperature (and

“knocking”) indicates excess air in tank. To correct this condition,
replace the diaphragm expansion tank.

Water System

If system is to remain out of service during freezing weather,

always DRAIN IT completely. Water left in to freeze will crack
pipes and/or boiler.

Tankless Coil (or Cover Plate Gasket)

The tankless coil gasket should be checked at least twice a year
for leakage and replaced if necessary.

BW

4

/BW

5

Summary of Contents for BW4

Page 1: ...hed to or shipped with unit and other safety precautions that may apply Recognize safety information This is the safety alert symbol When you see this symbol on unit or in instructions and manuals be alert to potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...by the boiler manufacturer and the expansion tank manufacturer 13 Expansion tank performance and life expectancy can be hindered by overfilling the boiler An initial fill pressure of 10 12 psig is recommended For higher fill pressures the expansion tank s air charge will need to be increased to match the fill pressure Consult the manufacturer s guidelines for sizing and selection 14 Purging the he...

Page 3: ... installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installer service agency fuel oil supplier or your distributor or branch for information or assistance The qualified installer or agency must use only factory authorized and list...

Page 4: ...ck with local authorities and obtain professional help where needed The Operation Instructions Final Checks and Adjustments and Maintenance sections in this manual are vital to the proper and safe operation of the heating system Take the time to be sure they are all done Locating the Boiler If boiler is part of a planned heating system locate it as close as possible to where it is shown on plan If...

Page 5: ... 6 8 460 N A BW4BAH210 BW4RAH210 4 126 111 97 0 90 86 0 8 X8 X15 17 3 4 6 9 5 8 533 N A 4 175 150 130 1 25 83 9 8 X8 X15 17 3 4 6 9 5 8 533 N A 4 210 178 155 1 50 82 4 8 X8 X15 17 3 4 6 9 5 8 533 N A BW4BAH280 BW4RAH280 5 168 147 128 1 20 86 5 8 X8 X15 21 6 11 1 2 620 N A 5 245 209 182 1 75 83 6 8 X8 X15 21 6 11 1 2 620 N A 5 280 236 205 2 00 82 0 8 X8 X20 21 6 11 1 2 620 N A Shaded areas are as s...

Page 6: ...CK OF OXYGEN WARNING UNIT LIFE REDUCTION HAZARD Failure to follow this warning could result in personal injury death and or property damage Air for combustion must not be contaminated by halogen compounds which include fluoride chloride bromide and iodide These elements are found in aerosol sprays detergents bleaches cleaning solvents salts air fresheners and other household products WARNING Enoug...

Page 7: ... a minimum free area of 1 sq in per 2000 Btuh of total input rating of all equipment in the enclosure 4 When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall not be less than 3 in Boilers With Tankless Heater Coil Boilers may be factory packaged with a tankless heater coil The u...

Page 8: ...th supply and return lines should be piped to the front section or both to the rear section The boiler should NOT be piped return line to the front supply line to the rear or vice versa as this will cause boiler water to short circuit heat exchanger The connections may require certain additional fittings and parts as shown on diagrams See Fig 9 10 and 11 If installing an entire new heating system ...

Page 9: ...LVE THROTTLING VALVE CIRCULATOR PUMP AQUASTAT S R MAIN SHUTOFF VALVE ADJUST THE TWO THROTTLINE VALVES TO MAINTAIN AT LEAST 120 O F IN THE BOILER RETURN THE THROTTLING VALVES ARE USED FOR BYPASS PIPING IF REQUIRED A01034 Fig 10 Bypass Piping Circulator on Supply FILTROL WITH AIR PURGER AUTOMATIC FILL VALVE SUPPLY TO SYSTEM SHUTOFF VALVE BOILER SERVICE FILL LINE WITH SHUT OFF VALVE RETURN FROM SYSTE...

Page 10: ... grounded ground rod C Electrical Power Supply ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Turn off electric power at fuse box before making any line voltage connections Follow local electric codes WARNING All electrical work must conform to local codes as well as the National Electrical Code If not familiar with wiring and codes in general have ...

Page 11: ...ype expansion tank a in the supply line with the circulator located after the expansion tank or b off the e3 4 in tapping provided on the top of the rear casting with the circulator mounted directly off the boiler s supply piping connection This configuration allows the circulator to pump away from the expansion tank for improved air elimination and system performance The air reliminator fitting o...

Page 12: ...e The delay solenoid valve provides the same shut down action of the standard solenoid valve plus on burner start up the delay solenoid valve remains closed for an additional 15 seconds This allows the burner fan motor to pre purge the combustion chamber and the oil pump to bring the supply oil pressure up to its set point helping to provide a clean light off Filling Boiler OPTION 1 A How a Hot Wa...

Page 13: ...vide air for combustion and operation of barometric draft control The room should be isolated from any area served by exhaust fans Do not install exhaust fans in this room See Fresh Air for Combustion section earlier in this document Draft Regulators Provided A draft regulator is required It should preferably be mounted in smoke pipe Use a draft gage to adjust to proper opening When burner air sup...

Page 14: ... PLATE WITNESS MARK BECKETT AFG VARIABLE V1 HEAD ADJUSTMENTS AND SETTINGS A06664 Fig 14 Beckett Burner Setting Variable V1 Head 5 32 GAP 7 16 ABOVE NOZZLE DIMENSION N SEE ABOVE BURNER F HEAD MODEL F0 THRU F31 DIMENSION N HEAD TO NOZZLE 1 16 BECKETT AFG BURNER ELECTRODE ADJUSTMENTS F HEADS A06665 Fig 15 Beckett Burner Setting Fixed F Head 140 210 A06506 Fig 16 Riello 40 F5 Burner Electrode Adjustme...

Page 15: ...kept clean and free of dirt lint and oil so as to maintain proper amount of air the fuel requires to burn NOTE If any component parts must be replaced always use parts recommended by burner manufacturer F Fan and Blower Housing Check burner blower wheel for dirt grease and grime Clean as necessary Check motor is attached to burner housing and wheel is attached tightly to motor shaft Check pump cou...

Page 16: ...n for some time recheck the whole system for leaks and recheck boiler and vent pipe for leaks Replace or patch any boiler seals that are faulty FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Never burn garbage or paper in the unit and never leave combustible material around it WARNING Relief Valve This valve should open automatically when system press...

Page 17: ...er and if applicable burner head 3 Remove the burner drawer assembly clean the electrodes and then reset the electrode spark gap per the manufacturer s recommendations 4 Replace the oil nozzle with the exact same size and type recommended for use on this boiler 5 Reinstall the burner drawer assembly making sure the head location and size if applicable are per the manufacturer s recommendations If ...

Page 18: ...ithout Tankless Coil AQUASTAT HIGH LIMIT CONTROLLER The aquastat control s high limit contacts open and turn off the burner when the boiler water temperature reaches the control s high limit set point The high limit contracts automatically reset after the boiler water temperature drops past the set point by 10_ F which is a fixed differential When the thermostat controls call for domestic space he...

Page 19: ...RING OIL BURNER MOTOR L8148A AQUASTAT IGN TRANS B W CIRCULATOR B W B W W B O B B R4184D RELAY Y Y CAD CEL IK1 JUMPER IK IK2 B2 C2 C1 ZC F F ZR B1 L2 T T T T G GND L1 HOT L2 L1 L2 B1 B2 C1 B R ZR B R W ZC C2 HIGH LIMIT 1K2 LOW LIMIT CIRCULATOR COLOR CODE BK BLACK O ORANGE Y YELLOW R RED W WHITE 1K1 1K A R LINE VOLTAGE CLASS II 24 VOLTS T T L2 L1 3 F F B 3 T T C1 C2 B2 B1 L2 L1 B R G B2 B1 C2 C1 COL...

Page 20: ...20 A06504 Fig 21 Boilers Without Tankless Coil and Honeywell L8148 Aquastat Control BW4 BW5 ...

Page 21: ...21 F5 only A06505 Fig 22 Boilers With Tankless Coil and Honeywell L8124C Aquastat Control and Riello Burners BW4 BW5 ...

Page 22: ...d or burner may be dirty Clean all flue passages and vent pipe Have burner cleaned and readjusted Burner may not be firing at proper rate Check nozzle size it there is any doubt Have burner adjusted Burner may be short cycling Short cycling too frequent off and on of burner causes sooting If boiler and or burner becomes Burner may be short cycling dirty at frequent intervals correct the dirt condi...

Page 23: ...ction 8 in X 12 in 4 section 8 in X 20 in 5 146 30 031 10 Collector Base 3 section 425 00 279 4 section 425 00 280 5 section 425 00 281 11 Tape Plym Collector insulation 1 in X 1 16 in X 100 Included in Part 425 00 279 80 81 12 Collector Top Included in part 425 00 279 80 81 13 Wing Nut 8 32 Brass 137 04 007 14 Screw 14 X 3 4 in HWH SL S M SC Hex Washer Head Slotted Sheet Metal Screw 146 95 109 15...

Page 24: ...chined 403 00 014 11 Washer Lock Plain 5 16 in 146 95 123 12 Bolt 5 16 in X 3 8 in Socket SH Shoulder BLT Bolt 1 4 in 20 TH Thread 146 95 122 Fig 24 Swing Fire Door Assembly Table 11 Beckett Oil Burner Service Parts OIL BURNER REPAIR PARTS BURNER NOT SHOWN PART NUMBER Burner Motor RP 015 00 Fuel Pump RP04501 Oil Solenoid Valve RP04601 Ignitor or Ignition Transformer RP02001 Oil Primary Control 718...

Page 25: ...4 3 XXX 4 XXX 2 1 5 1 6 4 7 21 9b 4 1 XXX A01042 Item Description 3 Section Part Number 4 Section Part Number 5 Section Part Number Complete Jacket 42670289AB 42670290AB 42670291AB 1 Panel Right Empire II 42570244AB 42570245AB 42570246AB 2 Jacket Panel Back 42570269AB 42570269AB 42570269AB 3 Jacket Panel Top 42570254AB 42570255AB 42570256AB 4 Panel Left Empire II 42570264AB 42570265AB 42570266AB 5...

Page 26: ... tankless coil 433 00 521 433 00 521 433 00 521 2b L8124C 1094 Aquastat Control with tankless coil 146 62 022 146 62 022 146 62 022 3a Taco 007 Circulator CI 001 03 CI 001 03 CI 001 03 3c Taco Circulator Gaskets 146 26 050 146 26 050 146 26 050 ____ 1 1 4 Flange set with gaskets nuts and bolts 146 26 049 146 26 049 146 26 049 4 Temperature Pressure Gauge 2 Stem 1260006 1260006 1260006 5a 1 1 4 x 2...

Reviews: