19
How A Hot Water System Operates
Entire heating system (boiler, piping, and radiation units)
is
fi
lled with water. As water in the boiler is heated, it
is circulated from top of boiler through supply main to
radiation units. Cooler water in radiation units
fl
ows back
through return piping through return main into the boiler.
This arrangement provides positive and rapid response to
the thermostat.
Filling The System With Water
OPTION #1
This method utilizes boiler piping as shown in
fi
gure on page 6.
A. Close
main shutoff valve, isolation valves, and zone
valves (if applicable). If bypass piping is installed,
also close two throttling valves. Leave boiler service
shutoff valve (if installed) and balancing valves to
each heating zone
fully open
.
B. Open
following valves in order: drain valve for power
purging, isolating valves before and after boiler
circulator (if applicable), both throttling valves (if
applicable), and then open
fi
ll line shutoff valve. Water
will
fi
ll bypass piping and push air through piping and
out power purging drain valve. When power purging
drain valve runs air free, close bypass piping throttling
valve (leaving throttling valve to supply piping fully
open).
C. Next,
open
isolation valve (or zone valve) to
fi
rst
zone. Water will
fi
ll piping and push any air out power
purging drain valve. When power purging drain valve
runs air free, close isolation valve or zone valve).
Repeat this procedure for remaining heating zones.
D. Once all zones are
fi
lled with water and purged of air,
close
power purging drain valve and
fi
ll line shut off
valve,
open
main shutoff valve, and
adjust
throttling
valves and balancing valves as required.
OPTION #2
• Close air vents on all radiation units.
• Open valves to radiation units. Verify boiler drain
valve, expansion tank drain cock, and air bleed screw
on expansion tank drain
fi
tting are closed.
• Open
fi
ll valve on piping to expansion tank.
• Open water inlet to boiler and leave it open.
• Open air vent on lowest radiation unit.
• When all air has escaped and water starts to
fl
ow from
vent, close it.
• Go to next radiation unit, and repeat this process until
fi
nishing with highest radiation unit.
• If heating system has automatic vents, this manual
venting is unnecessary but it will speed up proper
fi
lling
of the system.
If system is a closed expansion tank system, automatic
fi
ll
valve is needed. Leave automatic
fi
ll valve open to re
fi
ll
system automatically as needed.
Note initial
fi
ll pressure on boiler’s temperature / pressure
gauge, which should be 10-15 psig. Any lowering of
pressure from its initial
fi
ll pressure indicates loss of
water due to leakage. Automatic
fi
ll valve should then
compensate for this water pressure loss. If it does not,
manually open this valve to re
fi
ll system until needle is
again pointing to same pressure reading. Instructions are
packaged with valve.
FILLING THE BOILER
Summary of Contents for BW4BAH-91
Page 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...
Page 28: ...28 ELECTRICAL WIRING Figure 16 Honeywell L7248L Control With Beckett AFG Burner...
Page 29: ...29 Figure 17 Honeywell L7248L Control With Riello F5 F10 Burner ELECTRICAL WIRING...
Page 31: ...NOTES...
Page 32: ...CAC BDP 7310 West Morris St Indianapolis IN 46231...