23
Adjust Operating Controls
:
Use the following settings
for
fi
rst adjustment:
High Limit:
Baseboard and Convectors 200°F
Standing Radiators 180°F
Low Limit
(when used) 140º ( increase if hotter domestic
water is required, low limit set point must be at least 20°F less
than high limit set point)
Adjust Thermostat Heat Anticipator To: 0.2
Amp
s
Check Thermostat Operation:
Follow instructions included with your thermostat.
CHECKING AND ADJUSTING CONTROLS
NOTICE
You or your installer must follow these instructions
carefully.
WARNING
Burn, scald hazard. Do not attempt to start the
burner when excess oil has accumulated, when
the unit is full of vapor, or when the combustion
chamber is very hot.
!
Locate thermostat
fi
ve feet above the
fl
oor on inside wall.
Locate thermostat to sense average room temperature,
avoid the following:
THERMOSTAT LOCATIONS TO AVOID
DEAD
SPOTS
HOT SPOTS
COLD SPOTS
Behind
doors
Concealed pipes
Concealed pipes
or ducts
Fireplace
TV sets
Stairwells drafts
Corners &
alcoves
Radios
Doors drafts
Lamps
Unheated room
on other side of
wall
Direct sunlight
Kitchens
When temperature on thermostat is set above indicated
thermostat temperature, boiler’s burner should start. Verify
that when room temperature reaches selected temperature
setting, thermostat should turn boiler’s burner off, and once
room temperature falls few degrees boiler starts operating
again.
Do not start burner unless all cleanout doors are
secured in place.
Summary of Contents for BW4BAH-91
Page 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...
Page 28: ...28 ELECTRICAL WIRING Figure 16 Honeywell L7248L Control With Beckett AFG Burner...
Page 29: ...29 Figure 17 Honeywell L7248L Control With Riello F5 F10 Burner ELECTRICAL WIRING...
Page 31: ...NOTES...
Page 32: ...CAC BDP 7310 West Morris St Indianapolis IN 46231...