background image

7

Provide enough fresh air to assure proper combustion. 
Fire in the boiler uses oxygen. It must have continuous 
supply. Air in the house contains only enough oxygen to 
supply burner for short time. Outside air must enter the 
house to replace air used by the burner. Study the following 
examples 1 and 2 to determine your fresh air requirements.

EXAMPLE 1: Boiler Located in Unconfi ned Space

If your boiler is in an open area (un-partitioned basement) 
in conventional house, air that leaks through cracks around 
doors and windows will usually be adequate to provide air 
for combustion. Doors should not 

fi

 t tightly. Do not caulk 

cracks around windows.
An uncon

fi

 ned space is de

fi

 ned as space whose volume is 

not less than 50 cubic feet per 1,000 Btu per hour of total 
input rating of all appliances installed in that space.

EXAMPLE 2: Boiler Located in Confi ned Space

A. 

   

All Air from Inside the Building:

 Con

fi

 ned 

space shall be provided with two permanent openings 

communicating directly with additional room(s) of suf

fi

 cient 

volume so the combined volume of all spaces meets the 

criteria for uncon

fi

 ned space. Total input of all combustion 

equipment installed in combined space shall be considered 

in making this determination. Each opening shall have 

minimum free area of one square inch per 1,000 Btu per 

hour of total input rating of all combustion equipment in the 

con

fi

 ned space, but not less than 100 square inches. One 

opening shall be within 12 inches of top and one within 12 

inches of bottom of the enclosure.

Example: Your boiler is rated at 100,000 Btu per hour. 

Water heater is rated at 30,000 Btu per hour. Total is 

130,000 Btu per hour. You need two grilles, each with 130 

square inches of FREE opening. Metal grilles have about 

60% FREE opening. To 

fi

 nd louvered area needed, multiply 

free opening required by 1.7 (130 x 1.7 = 221.0 sq. in. 

louvered area). In this example, two grilles each having 8” 
x 30” (240 sq. in.) louvered area would be used.

FRESH AIR FOR COMBUSTION

 WARNING

Asphyxiation, 

fi

 re hazard. Do not obstruct air 

openings to combustion area. Follow instructions 

below, to maintain adequate combustion air.

!

  

NOTICE

Install outside air intake if you use 

fi

 replace or 

kitchen or bathroom exhaust fan. These devices rob 

boiler and water heater of combustion air.

Figure 4 - Air Openings For Boiler Located In 

Confi ned Space (Utility Room

)

Summary of Contents for BW4BAH-91

Page 1: ...0 BW4RAH 140 BW5BAH 140 BW5RAH 140 BW4BAH 126 BW4RAH 126 BW5BAH 126 BW5RAH 126 BW4BAH 175 BW5RAH 175 BW5BAH 175 BW5RAH 175 BW4BAH 210 BW4RAH 210 BW5BAH 210 BW5RAH 210 Models Series C BW4BAH 168 BW4RAH...

Page 2: ...fety relief valve drain valve flue brush and extra boiler tap for expansion tank or air elimination SAFETY NOTICES Boiler installation shall be completed by qualified agency NOTICE Used to address pra...

Page 3: ...183 84 3 5 13 7 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the...

Page 4: ...es of steam and hot water which may damage the surroundings Before installing the safety relief valve read the manufacturer s instructions and maintenance section of the manual on safety relief valves...

Page 5: ...where passage is required for access to another side for cleaning servicing inspection or replacement of any parts that normally may require such attention Boilers must be installed at least 6 from co...

Page 6: ...IRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL...

Page 7: ...ts the criteria for unconfined space Total input of all combustion equipment installed in combined space shall be considered in making this determination Each opening shall have minimum free area of o...

Page 8: ...he enclosure 3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in t...

Page 9: ...ler See figure 6a A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install discharge piping from safety relief va...

Page 10: ...emperatures of less than 120 F Condensation is corrosive and can eventually cause damage to boiler and venting system Minimum design return water temperature to prevent this condensation in boiler and...

Page 11: ...M EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1...

Page 12: ...MPS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Ar...

Page 13: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Fig...

Page 14: ...ine controls are used Tankless coils are meant to provide domestic hot water for intermittent draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or o...

Page 15: ...mption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section Total Volume Gallon...

Page 16: ...SIZES FIRING RATE gph CHIMNEY HEIGHT ft NOMINAL CHIMNEY ROUND LINER INSIDE SQUARE LINER INSIDE 0 60 1 30 15 8 x 8 6 6 x 6 1 31 1 80 15 8 x 8 7 6 x 6 1 81 2 00 20 8 x 8 8 6 x 6 For elevations above 2 0...

Page 17: ...Connection Minimum height Must be at least 3ft 9m higher than highest part of passage through roof Must be at least 2ft 7m higher than any neighboring object within 10ft 3m Must have unobstructed top...

Page 18: ...regulations Connect 115 volt electrical supply to L1 and L2 terminals on limit and two thermostat wires to T and T terminals on same limit See wiring diagram page 28 Run separate circuit from separate...

Page 19: ...ing drain valve runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain v...

Page 20: ...r must be installed in fuel unit Refer to fuel unit instructions furnished with burner for specific instructions on installing bypass plug Do not exceed fuel unit manufacturer s recommendations for ru...

Page 21: ...175 1 00 80 A 1 25 F6 1 NO 10 0 3 AFG F HEAD 140 BW 4 5 BAH 210 1 25 80 A 1 50 F6 1 NO 10 2 3 AFG F HEAD 140 BW 4 5 BAH 168 1 00 60 B 1 20 0 NO 10 1 5 2 AFG 50 MD 140 BW 4 5 BAH 245 1 50 45 B 1 75 2...

Page 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...

Page 23: ...e unit is full of vapor or when the combustion chamber is very hot Locate thermostat five feet above the floor on inside wall Locate thermostat to sense average room temperature avoid the following TH...

Page 24: ...ent that may lodge on valve seat Permit valve to snap shut Refer to valve manufacturer s instructions packaged for more details Conventional Expansion Tank Tank may become water logged or may receive...

Page 25: ...tions from combustion chamber area take care to not damage any of refractory or blanket insulation To gain access to combustion chamber first check that shut off valve on fuel oil line is closed and d...

Page 26: ...assembly make sure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 In...

Page 27: ...k to be sure electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It...

Page 28: ...28 ELECTRICAL WIRING Figure 16 Honeywell L7248L Control With Beckett AFG Burner...

Page 29: ...29 Figure 17 Honeywell L7248L Control With Riello F5 F10 Burner ELECTRICAL WIRING...

Page 30: ...burner fan motor to pre purge combustion chamber and oil pump to bring supply oil pressure up to its set point helping to provide clean light off LIMIT CONTROL provided Refer to manufacturer instructi...

Page 31: ...NOTES...

Page 32: ...CAC BDP 7310 West Morris St Indianapolis IN 46231...

Reviews: