7
Provide enough fresh air to assure proper combustion.
Fire in the boiler uses oxygen. It must have continuous
supply. Air in the house contains only enough oxygen to
supply burner for short time. Outside air must enter the
house to replace air used by the burner. Study the following
examples 1 and 2 to determine your fresh air requirements.
EXAMPLE 1: Boiler Located in Unconfi ned Space
If your boiler is in an open area (un-partitioned basement)
in conventional house, air that leaks through cracks around
doors and windows will usually be adequate to provide air
for combustion. Doors should not
fi
t tightly. Do not caulk
cracks around windows.
An uncon
fi
ned space is de
fi
ned as space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour of total
input rating of all appliances installed in that space.
EXAMPLE 2: Boiler Located in Confi ned Space
A.
All Air from Inside the Building:
Con
fi
ned
space shall be provided with two permanent openings
communicating directly with additional room(s) of suf
fi
cient
volume so the combined volume of all spaces meets the
criteria for uncon
fi
ned space. Total input of all combustion
equipment installed in combined space shall be considered
in making this determination. Each opening shall have
minimum free area of one square inch per 1,000 Btu per
hour of total input rating of all combustion equipment in the
con
fi
ned space, but not less than 100 square inches. One
opening shall be within 12 inches of top and one within 12
inches of bottom of the enclosure.
Example: Your boiler is rated at 100,000 Btu per hour.
Water heater is rated at 30,000 Btu per hour. Total is
130,000 Btu per hour. You need two grilles, each with 130
square inches of FREE opening. Metal grilles have about
60% FREE opening. To
fi
nd louvered area needed, multiply
free opening required by 1.7 (130 x 1.7 = 221.0 sq. in.
louvered area). In this example, two grilles each having 8”
x 30” (240 sq. in.) louvered area would be used.
FRESH AIR FOR COMBUSTION
WARNING
Asphyxiation,
fi
re hazard. Do not obstruct air
openings to combustion area. Follow instructions
below, to maintain adequate combustion air.
!
NOTICE
Install outside air intake if you use
fi
replace or
kitchen or bathroom exhaust fan. These devices rob
boiler and water heater of combustion air.
Figure 4 - Air Openings For Boiler Located In
Confi ned Space (Utility Room
)
Summary of Contents for BW4BAH-91
Page 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...
Page 28: ...28 ELECTRICAL WIRING Figure 16 Honeywell L7248L Control With Beckett AFG Burner...
Page 29: ...29 Figure 17 Honeywell L7248L Control With Riello F5 F10 Burner ELECTRICAL WIRING...
Page 31: ...NOTES...
Page 32: ...CAC BDP 7310 West Morris St Indianapolis IN 46231...