DISpLAy pANEL

TABLE 1 – Display panel

Indicator

Light

Function

Off

Humidifier is turned off or not receiving power .

Solid 

Green

Humidifier is turned on .

Flashing 

Green

Humidifier is preparing to turn on . Occurs if power is 
disconnected, then restored with switch ON . Flashes for 
one minute .

Solid 

Green

Normal Operation . Fill valve is energized allowing water 
to flow into canister via fill cup . (Does not illuminate when 
tempering water during drain cycle .)

Flashing 

Green

Fill and Drain Valves are pulsing to dislodge mineral build-up 
in canister . Flashes 10 times in four seconds .

Solid Red

Fault Mode . Indicates canister needs water but cannot fill . 
Humidifier shuts down . (Occurs if high water probe does not 
detect water after fill valve is energized for 40 minutes .) 

Solid 

Green

Normal Operation . Humidistat is calling for steam and 
humidifier is operating .

Solid 

yellow

Humidifier is operating but is not delivering steam at rated 
capacity . Occurs if humidifier has operated for 168 hours 
at less than rated capacity due to low water conductivity . 
Light will turn green once water conductivity increases and 
humidifier is delivering rated capacity .

Flashing 

Green

Humidifier is preparing to drain . (Fill valve is open 
tempering water in canister .) Occurs when humidifier 
is turned off, at end of season drain (72 hours with no 
operation) and during forced drain down (168 hours of 
operation with no drain activity .) 

Fill and Drain Valves are pulsing to dislodge mineral build-up 
in canister . Flashes 10 times in four seconds .

Solid 

Green

Drain valve is energized and open, draining canister . Valve 
remains energized for four minutes .

Indicates end of season shut-down . Occurs if humidifier 
does not receive call for humidity in 72 hours . Light remains 
on for 24 hours . 

Flashing 

Red

Canister has reached the end of its life and needs to be 
replaced . Occurs after humidifier has operated for at least 
168 hours and for an additional 24 hours at a current level 
below 75% of the maximum operating current . Humidifier 
continues to operate, but at reduced capacity .

Solid Red

Operational problem with humidifier . Humidifier shuts 
down . Occurs when unit detects over-current which can be 
caused by failure to drain or other system failures . Call your 
heating and air conditioning dealer for service .

HUMIDIFIER CONTROL & OpERATING INSTRUCTIONS

The control provided with your humidifier is mounted either in your return 
air duct or on a wall in the living space . The control has a set of contacts 
which close when the RH is below the set point . That signal tells the 
humidifier to energize the electrodes in the canister to generate steam, 
provided the indoor unit blower is on . If the blower activation relay is 
installed, a call for humidity will turn on the indoor unit blower .
It is important to anticipate changes in outdoor temperature and adjust 
the setting accordingly to avoid excessive condensation when outdoor 
temperature is low . For example, with an outdoor temperature of 20°F the 
correct setting will be 35% . If the temperature is expected to fall to 0°F 
that evening, then merely reduce the setting to 25% several hours prior to 
the temperature change .
See 

Table 2

 for the recommended settings . These settings, which are 

based on years of research, represent a compromise between humidity 
levels that would be most desirable for comfort and humidity levels that 
are suitable for protection of your home and to avoid condensation on 
your windows . For example, a wintertime indoor humidity of 50% may be 
considered ideal for comfort, but unfortunately, it probably would result 
in condensation, which can cause damage to your home . Observing the 
recommended humidity levels on your Humidifier Control is an important 
safeguard . Condensation of water on the inside surface of windows in 
the form of fogging or frost is usually an indication of too much humidity . 
This same condensation can occur in other areas in your home, possibly 
resulting in damage .

TABLE 2 – Outdoor Temperature/Indoor Relative Humidity

 

Outside Temperature  

Recommended RH

 +40°F 

45%

 +30°F 

40%

 +20°F 

35%

 +10°F 

30%

 0°F 

25%

 –10°F 

20%

 –20°F 

15%

Summary of Contents for HUMXXSTM3034

Page 1: ...READ AND SAVE THESE INSTRUCTIONS Model HUMXXSTM3034 Residential Steam Humidifier Owner s Manual Includes Safety Operating Instructions Residential Steam Humidifier ...

Page 2: ... until electrical power is disconnected Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system Electrical shock hazard If the humidifier starts up responding to a call for humidity during maintenance severe bodily injury or death from electrical shock could occur Follow the procedures in this manual before performing service or ma...

Page 3: ...m and Canister 90 1522 Steam Outlet Drain Supply Water Drain Cup Drain Valve Canister Electrodes High Water Level Sensor Flow Control Orifice Inlet Fill Valve Overflow Fill Fill Cup Thank you for your recent steam humidifier purchase We appreciate your business and are pleased to add your name to our growing list of customers You have invested in the highest quality equipment available Your humidi...

Page 4: ...s time the Steam light illuminates green If the humidifier cannot produce steam at the rated level after trying for 168 hours the Steam light illuminates yellow The humidifier continues to operate in this state until the rated output is reached The conductivity of naturally soft water hard water and softened water changes as the water heats up but the internal controller adjusts the water level to...

Page 5: ...rent level below 75 of the maximum operating current Humidifier continues to operate but at reduced capacity Solid Red Operational problem with humidifier Humidifier shuts down Occurs when unit detects over current which can be caused by failure to drain or other system failures Call your heating and air conditioning dealer for service HUMIDIFIER CONTROL OPERATING INSTRUCTIONS The control provided...

Page 6: ...obe conductor 5 Loosen hose clamp at top of canister 6 Slide hose off top of canister 7 Slide canister up and out of drain assembly Discard canister 8 Remove o ring from drain assembly using small screw driver 9 Inspect drain assembly and remove any debris See drain valve cleaning procedure in Installation Maintenance manual 10 Insert new o ring into slot in drain assembly O ring is provided with ...

Page 7: ...Form OG HUMXXSTM 01 10009952 B2205831A 10 12 2012 CAC BDP 7310 West Morris St Indianapolis IN 46231 ...

Reviews: