21
LOCATION 175: PROGRAMMING ZONES 1,2,7, & 8 FOR NORMALLY CLOSED OPERATION ONLY
Location 175 is used to program zones 1,2,7, & 8 for normally closed operation only, eliminating the need for the end
of line resistors on these zones. When a zone is programmed for normally closed operation, a short on that zone will
not change the loop condition, and an open on that zone will produce a faulted condition. This feature will be ignored by
any Priority zone. To program a zone for normally closed only, refer to the chart on the following page, and program
the appropriate data in this location.
ZONES TO PROGRAM FOR N/C OPERATION
DATA T0 PROGRAM IN LOCATION 175
2
"1"
1
"2"
2 & 1
"3"
7
"4"
7 & 2
"5"
7 & 1
"6"
7, 2, & 1
"7"
8
"8"
8 & 2
"9"
8 & 1
A = "10"
8, 2, & 1
B = "11"
8 & 7
C = "12"
8, 7, & 2
D = "13"
8, 7, & 1
E = "14"
8, 7, 1, & 2
F = "15"
LOCATION 176: SPLIT REPORTING - PROGRAMMING TAMPER, DOWNLOAD COMPLETE, AND AUTOTEST
TO REPORT TO THE SECONDARY PHONE NUMBER
The 8980 is capable sending certain reports to the secondary telephone number. This feature known as split reporting
can be used to send alarm reports to one number and supervisory reports to another number. When using split
reporting with the 8980, the primary telephone number always takes priority over the secondary telephone number.
The 8980 always sends zone and alarm reports to the primary telephone number. There are 7 reports that can be
programmed to report to the second telephone number. Location 176 is used to force up to three of these individual
reports to the second telephone number. To program tamper, download complete, or autotest to report to the
secondary telephone number, use the following chart and program the appropriate number in location 176.
REPORTS TO SEND TO SECONDARY NUMBER
DATA T0 PROGRAM IN LOCATION 176
AUTOTEST
"2"
DOWNLOAD COMPLETE
"4"
DOWNLOAD COMPLETE ; AUTOTEST
"6"
TAMPER
"8"
TAMPER ; AUTOTEST
A = "10"
TAMPER ; DOWNLOAD COMPLETE
C = "12"
TAMPER ; DOWNLOAD COMPLETE ; AUTOTEST
E = "14"