LOCATION 177: SPLIT REPORTING - PROGRAMMING AC POWER FAIL, LOW BATTERY, OPEN/CLOSE, AND
MAINTENANCE OPEN/CLOSE TO REPORT TO THE SECONDARY PHONE NUMBER
The 8980 is capable sending certain reports to the secondary telephone number. This feature known as split reporting
can be used to send alarm reports to one number, and supervisory reports to another number. When using split
reporting with the 8980, the primary telephone number always takes priority over the secondary number. The 8980
always sends zone and alarm reports to the primary number. There are 7 reports that can be programmed to report to
the second telephone number. Location 177 is used to force up to four of these individual reports to the second
number. To program AC power fail, low battery, open/close, or maintenance code open/close to report to the
secondary number, use the following chart and program the appropriate data in this location.
REPORTS TO SEND TO SECONDARY NUMBER
DATA FOR LOCATION 177
MAINT CODE OPEN/CLOSE
"1"
OPEN/CLOSE
"2"
OPEN/CLOSE; MAINT CODE OPEN/CLOSE
"3"
LOW BATTERY
"4"
LOW BATTERY; MAINT CODE OPEN/CLOSE
"5"
LOW BATTERY; OPEN/CLOSE
"6"
LOW BATTERY; OPEN/CLOSE; MAINT CODE OPEN/CLOSE
"7"
AC FAIL
"8"
AC FAIL; MAINT CODE OPEN/CLOSE
"9"
AC FAIL; OPEN/CLOSE
A ="10"
AC FAIL; OPEN/CLOSE; MAINT CODE OPEN/CLOSE
B ="11"
AC FAIL; LOW BATTERY
C ="12"
AC FAIL; LOW BATTERY; MAINT CODE OPEN/CLOSE
D ="13"
AC FAIL; LOW BATTERY; OPEN/CLOSE
E ="14"
AC FAIL; LOW BATTERY; OPEN/CLOSE; MAINT CODE OPEN/CLOSE
F ="15"
LOCATION 178: PROGRAMMING THE SECONDARY ENTRY DELAY (ZONE TYPE 9)
Location 178 contains the number of 10-second increments in the secondary entry delay. This delay can be
programmed from 10 to 150 seconds ("1" = 10 sec thru "15" = 150 sec).
LOCATION 179: PROGRAMMING THE SECONDARY EXIT DELAY (ZONE TYPE 9)
Location 179 contains the number of 10 second increments after arming, before trips will be recognized on a zone type
9. The exit delay can be programmed in 10 second increments from 10 to 150 seconds ("1" = 10 seconds thru "15" =
150 seconds). (Note: A "0" entry is treated as zero (0) seconds). If the exit delay time in this location is less than that
of location 076, this secondary delay will follow the amount of time in location 076.
LOCATION 180: PROGRAMMING THE LOOP RESPONSE TIME
Location 180 is used to program the loop response time for all zones programmed as fast loop response in locations
186-193. The response time is equal to 20 milliseconds times the number programmed in this location ("1" = 20
milliseconds and "5" = 100 milliseconds). If this location contains a "0", the loop response time will be 500 milliseconds.
LOCATIONS 181-185: DO NOT PROGRAM THESE LOCATIONS (each should be "0")