THE FOLLOWING LOCATIONS ARE ACCESSIBLE ONLY THROUGH DOWNLOADING

 

 

LOCATIONS 186-193: CONTROL PANEL ACCESS CODE

 

 
Locations 186-193 contain the eight digit access code the 8980 must receive from the downloading software before the 
panel will permit downloading to occur. The factory default code is listed in the instructions provided with the CADDX 
download software package.  
 

LOCATIONS 194-209: CALL BACK TELEPHONE NUMBER

 

 
The presence of a phone number in locations 194-209 will cause the control panel to dial back this number after a 
successful panel access code has been entered. If a telephone number is present, the control panel will hang up for 
approximately 36 seconds (insuring that the calling party has disconnected), then it will call back. Any zero (0) within 
the telephone number must be programmed as an "A". If tone dialing is desired, program an "F" in the location where 
tone dialing should begin. If the entire number should be tone dialing, program an "F" in location 194. Four second 
delays can be obtained anywhere in the sequence by programming a "D" in the appropriate delay location. WARNING: 
CALLBACK PHONE NUMBER SHOULD ALWAYS BE REVIEWED FOR ACCURACY BEFORE DISCONNECTING. 
 

LOCATION 210: ANSWERING MACHINE DEFEAT

 

 
Location 210 contains the answering machine defeat enable. To defeat an answering machine, two telephone calls 
must be made to the premises. On the first call, let the phone ring the same number of times (or less) as the number 
programmed in location 210 (maximum 3). The control panel will detect these rings and start a 45 second timer. If a 
call comes in during that 45 second time frame, the control panel will answer on the first ring.  To disable this feature, 
program a "0" in this location. 
 

LOCATION 211: LOCAL PROGRAMMING LOCKOUT

 

 
Location  211  is  used  to  disable  local  programming  lockout.  If  a  "5"  is  programmed  in  this  location,  all  local 
programming is locked out. If an "A" is programmed in this location, all programming functions related to the digital 
communicator will be locked out. Any other number in location 211 will allow all local programming. 
 

LOCATION 212: CONTROL PANEL SHUTDOWN

 

 
Location 212 is used to shut down the control panel. Programming an "A" in this location will completely shutdown the 
control panel. The keypad will appear "dead", and the siren and communicator will not operate. WARNING: 
EXTREME CARE SHOULD BE TAKEN NOT TO INADVERTENTLY PROGRAM THIS LOCATION. 
 
 
 
 
 

 

ALARM HISTORY

 

 

 

NOTE: SYSTEM MUST BE DISARMED TO INITIATE ALARM HISTORY

.  Five seconds after pressing the [0] key, the 

keypad will annunciate “Freeze Frame” alarm history.  The zone LED’s will indicate which zone(s) caused the last 
alarm  regardless  of  the  number  of  times  the  Ranger  8980  has  been  armed  or  disarmed  since  that  alarm.    It 
annunciates by blinking the zone LED(s) that caused the alarm, and lighting steady those that were bypassed when 
that alarm occurred.  The annunciation will continue for 5 seconds.  Alarm History is erased when the Ranger 8980 is 
put into the program mode.  A burglary zone that has been bypassed due to “Swinger Shutdown” will alternate between 
continuous and blinking. 
 
 

Summary of Contents for Ranger 8980

Page 1: ...PTION 4 HOW TO PROGRAM THE RANGER 8980 6 KEYPAD PROGRAMMING EXAMPLES 7 PROGRAMMING PHONE NUMBERS FORMATS 8 9 COMMUNICATOR FORMAT SELECTION GUIDE 9 OPTIONAL PROGRAMMING INSTRUCTIONS 10 22 AVAILABLE ZON...

Page 2: ...he Ranger 8980 functions After installation of the security system complete the information on page 1 of the users manual and explain the system operation to all security system owners operators Stand...

Page 3: ...3 PARTS DIAGRAM...

Page 4: ......

Page 5: ...e Ring red 20 R1 House Telephone Ring gray 21 22 Siren driver output to speaker s speaker rating should be 15 watt at 8 or 16 ohm or 30 40 watt at 4 8 or 16 ohms If siren driver disable is selected in...

Page 6: ...icating the data in that location to be 6 If no LED s are illuminated the location contains a 0 To advance from location 000 through 180 press the key To go to a specific location press the location n...

Page 7: ...8...

Page 8: ...1800HZ 2300HZ Fast with Parity and Hex Capability requires a 9 in this location If you need another format choose from those listed on the format table located on page 13 and program the data in loca...

Page 9: ...Z HANDSHAKE DOUBLE ROUND PARITY 20 PPS 5 EXTENDED RADIONICS SLOW 1800HZ TRANSMIT 2300HZ HANDSHAKE DOUBLE ROUND PARITY 20 PPS EXTENDED HEX CAPABILITY 6 EXTENDED RADIONICS SLOW 1800HZ TRANSMIT 1400HZ HA...

Page 10: ...GITS With the Ranger 8980 disarmed the Go To Program access code can be used to enter the program mode To disable the Go To Program access code program a 15 in location 028 The factory default setting...

Page 11: ...8980 is armed or disarmed An open will create a Trouble condition Keypad LED will be steady for FIRE and flashing for Trouble 9 SECONDARY DELAY A secondary delay zone works like an entry exit delay zo...

Page 12: ...rammed in location 094 is sent as the ones digit The tens digit is programmed in location 095 LOCATION 096 097 PROGRAMMING TO REPORT DOWNLOADING COMPLETE Locations 096 097 contain the communicator rep...

Page 13: ...ZONE 4 Locations 110 111 contain the communicator code to be reported each time zone 4 creates an alarm Location 110 contains the standard digit and location 111 contains the extended digit When usin...

Page 14: ...a bypass immediately When a bypass is removed a restore will be reported if Restore is enabled in location 126 LOCATION 126 PROGRAMMING THE COMMUNICATOR CODE FOR RESTORAL Location 126 contains the co...

Page 15: ...he following procedure First remove the jumper marked voltage siren on the PC board Next program a 1 in location 132 Finally replace the jumper in the voltage position Terminals 21 22 will now output...

Page 16: ...d a 1 is programmed in location 141 all reports will be double line extended If location 141 contains a 0 only non alarm reports will be extended restore cancel opening closing bypass and trouble With...

Page 17: ...ORITY SIREN RECYCLED OUTPUT 4 ARMED WITH BYPASS LATCHED OUTPUT 5 AC POWER LATCHED OUTPUT 6 LOW BATTERY LATCHED OUTPUT 7 ALARM MEMORY LATCHED OUTPUT 8 ENTRY LATCHED OUTPUT 9 EXIT MOMENTARY OUTPUT LOCAT...

Page 18: ...55 contains the current year ones digit If the current year is 1994 this location should contain a 4 which is the ones digit of the current year If the current year is 1995 this location should contai...

Page 19: ...t of the minutes after the hour that the autotest is desired The time is entered in 24 hour time If the desired autotest time is 5 25 PM the 24 hour time is 17 25 so this location should contain a 2 w...

Page 20: ...ime user number 7 arms the control The desired closing code should be programmed in this location This feature can be used in conjunction with the rotating maintenance code to give a closing report ea...

Page 21: ...ST TO REPORT TO THE SECONDARY PHONE NUMBER The 8980 is capable sending certain reports to the secondary telephone number This feature known as split reporting can be used to send alarm reports to one...

Page 22: ...9 AC FAIL OPEN CLOSE A 10 AC FAIL OPEN CLOSE MAINT CODE OPEN CLOSE B 11 AC FAIL LOW BATTERY C 12 AC FAIL LOW BATTERY MAINT CODE OPEN CLOSE D 13 AC FAIL LOW BATTERY OPEN CLOSE E 14 AC FAIL LOW BATTERY...

Page 23: ...umber programmed in location 210 maximum 3 The control panel will detect these rings and start a 45 second timer If a call comes in during that 45 second time frame the control panel will answer on th...

Page 24: ...SECONDARY ACCOUNT CODE 0 DISABLED 074 9 SECONDARY FORMAT 0 DISABLED CONTROL COMMUNICATOR FEATURES LOCATION PAGE DESCRIPTION DATA DEFAULT 075 10 ENTRY DELAY TIME 10 SECOND INCREMENTS 3 30 SECONDS 076...

Page 25: ...ANT ARMING 0 DISABLED 132 15 SIREN DRIVER OR VOLTAGE OUTPUT 0 SIREN DRIVER 133 15 LED EXTINGUISH FEATURE 0 DISABLED 134 15 NUMBER OF DIAL ATTEMPTS 8 EIGHT ATTEMPTS 135 15 POWER UP CONDITION 0 LAST CON...

Page 26: ...DIGIT 4 0 172 20 USER 7 MAINTENANCE CODE OPENING REPORT 0 DISABLED 173 20 USER 7 MAINTENANCE CODE CLOSING REPORT 0 DISABLED 174 20 PROGRAM ZONES 3 THRU 6 FOR NORMALLY CLOSED OPERATION 0 SUPERVISED 17...

Page 27: ...rect the situation The customer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES The telephone com...

Page 28: ...G IF ANY DEFECT APPEARS DURING THE WARRANTY PERIOD RETURN IT TO CADDX POSTAGE PREPAID THE UNIT WILL BE REPAIRED AND RETURNED FOR THE REMAINING 36 MONTHS OF WARRANTY THE UNIT WILL BE REPAIRED FOR A FEE...

Reviews: