EXtERNAL AIR INLEt
Fig. 7 -
Direct air inflow
LEGEND
1
Room to ventilate
2
External air inlet
• The room must be endowed with an external air recycling for a good climate in your ambient.
• The air inflow from outside to the inner occurs directly, through an opening on the external wall of the room
).
• Bedrooms, garages, and store of flammable materials are excluded.
• The air inlet should have a total net surface of 80 sqcm
2
: the aforesaid surface is to widen if inside the room
there are other activated appliances (for example: electric ventilators for foul air suction, cooker hoods, other
stoves, etc...) which depress the environment.
• At switched on appliance it is necessary to check that the pressure fall between the room and the outside
does not exceed 4,0 Pa value: if necessary widen the air inlet (EN 13384).
• The air inlet must be realized at a height close to the floor with an external grid against birds. In such a way it
cannot be obstructed by any object.
•
In case of installation with sealed-chamber the air inlet is not necessary.