31
vEGA - sIRE
3
pLUs - DoGE
3
pLUs - sFERA
3
- sFERA
3
pLUs - pRINCE
3
- pRINCE
3
pLUs - GLoBE - tREND - ELIsE
3
pLUs
EN
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and the is in "OFF".
• Check the type of glitch as
.
• Clean the burning pot and start the stove up again with P4 key.
13.5
"FAN FAILURE" ALARM
"ACTIVE ALARM" "AL 4 - FAN FAILURE": the fume fan is out of order.
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and the is in "OFF".
• Check the type of glitch as
.
• Clean the burning pot and start the stove up again with P4 key.
13.6
"FAILED IGNItIoN" ALARM
"ACTIVE ALARM" "AL 5 - FAILED IGNITION": the temperatureis not sufficient for ignition.
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and the is in "OFF".
• Check the type of glitch as
.
• Clean the burning pot and start the stove up again with P4 key.
13.7
"No pELLEt" ALARM
If the fume probe registers a temperature at the exhaust lower than the minimum threshold and the display
shows "ACTIVE ALARM" "AL 6 - NO PELLET".
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and the is in "OFF".
• Full the hopper.
• Clean the burning pot and start the stove up again with P4 key.
13.8
"tHERMAL sAFEtY" ALARM
In the hopper is installed an automatic thermostat which activates if the temperature excursion exceeds the
allowed limits, so avoiding the possibility that the pellet inside the hopper could burn because of overheating.
"ACTIVE ALARM" "AL 7 - THERMAL SAFETY": the thermostat stops the power supply to the auger.
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and then is in "OFF".
• Check the type of glitch as
.
• Unscrew the black cap, press the button and screw the cap again.
• Clean the burning pot and start the stove up again with P4 key.
13.9
"FAILURE DEpREss" ALARM
To the boiler is connected a pressostat which control the depression and in some stove models on the fire door
id installed a microswitch which registers the opening.
"ACTIVE ALARM" "AL 8 - FAILURE DEPRESS": the pressostat and/or fire door which is not correctly closed stops the
power supply to the auger.
• Reset the error with P4 key. The stove carries out the phase "FINAL CLEANING" and then is in "OFF".
• Check the type of glitch as
.
• Unscrew the black cap, press the button and screw the cap again.
• Clean the burning pot and start the stove up again with P4 key.
13.10
"DooR opEN" ALARM
On the lower part of the fire door is installed a microswitch which detects the opening.
"ACTIVE ALARM" "AL 9 - DOOR OPEN": it means that the fire door is not correctly closed.
• Reset the error pressing P4 key. The stove carries out a "FINAL CLEANING" and "OFF" appears.
• Check the type of failure as shown on
.
• Clean the burning pot and start the stove up again pressing P4 key.
14
MAINtEINANCE
14.1
INtRoDUCtIoN
For a long working life of the stove, have a periodic cleaning of the stove as described in the following paragrafs.
• Fume outlet pipes (fume c chimney flue + chimney pot) must always be cleaned, scrubbed and
checked by an authorized technician in compliance with local regulations, with the instructions of the
manufacturer and those of your insurance company.
• If there are no local regulations and no instruction from your insurance company, it is necessary to have your
fume pipe, chimney flue and chimney pot cleaned at least once a year.
• It is also necessary to have the combustion chamber, motors and fans cleaned and to have the gaskets and
the electronical elements checked at least once a year.
Summary of Contents for DOGE3 PLUS
Page 47: ...NOTE ...