KOBE-FENICE-SPARK-INDACO-PRINCE
10
LEGEND
Fig. 10
U
Insulation
V
Possible diameter increase
I
Inspection cap
S
Inspection access panel
P
Air inlet
T
Tee fitting with inspection cap
A
Distance from flammable material (smoke duct plate)
B
Maximum 4 m
C
Minimum 3° slope
D
Distance from flammable material (appliance plate)
E
Reflux area
F
Air ducting
The instructions in this chapter refer explicitly to the Italian installation regulation UNI 10683. In any case,
always observe the regulations in force in the country of installation.
6
INSTALLATION
6.1
INTRODUCTION
The heating system (gen combustion air combustion product expulsion any hydraulic/
aeraulic system) must be installed in compliance with the laws and regulations in force (*), and carried out by a
qualified technician, who must issue a declaration of conformity of the system to the system manager and shall
undertake full responsibility for final installation and consequent good operation of the product.
The manufacturer declines all responsibility in the event of installations that do not comply with the laws and regulations in force
and inappropriate use of the appliance.
In particular one must ensure that:
• the environment is suitable for installing the appliance (floor load-bearing capacity, presence or possibility of creating an ade-
quate electrical/hydrauic/aeraulic system when required, volume compatible with the appliance characteristics, etc.);
• the appliance is connected to a smoke expulsion system correctly sized according to EN 13384-1, which is resistant to soot fire
and which complies with the distances prescribed by the combustible materials indicated on the plate data;
• there is a suitable combustion air flow to the appliance;
• other combustion appliances or extraction devices installed do not cause a negative pressure of more than 4 Pa in the room
where the product is installed compared to the outside (only sealed appliances are allowed a maximum of 15 Pa of negative
pressure in the room).
(*)
The national reference standard for the installation of domestic appliances is UNI 10683 (IT) - DTU NF 24.1 (FR) - DIN 18896 (DE) -
NBN B 61-002 (BE) - Real Decreto 1027/2007 (ES) - Paesi Bassi (NL) Bouwbesluit - Danmark (DK) BEK n° 541 del 27/04/2020.
In particular, it is recommended to strictly observe the safety distances from combustible materials to avoid se-
rious harm to people and to the integrity of the home.
Installation of the appliance must ensure easy access to service the appliance itself, the smoke channels and the flue.
Always maintain adequate distance and protection in order to prevent the product from coming into contact with water.
It is forbidden to install the stove in rooms with a fire hazard.
With the exception of sealed installations, it is also forbidden for liquid fuel appliances with continuous or inter-
mittent operation that draw the combustion air from the room they are installed in or B-type gas heating applian-
ces, with or without the production of domestic hot water, to coexist in the same room or in interconnecting rooms.
Sealed installation means that the product is certified as sealed and its installation (ducting
of the combustion air and connection to the chimney) is airtight with respect to the installa-
tion environment.