Delivery, handling, reception and storage 

 

Delivery 

Kitchen  hoods  are  bulky  units

;  it  is  the  buyer’s 

responsibility to coordinate adequately the delivery on 
site in order to have the best mode of transport such 
as flat bed, small truck for narrow access or tailgates. 

 
Handling 

The buyer must provide necessary equipment on site 
to unload the truck.  When using a forklift for any item 
over  6  foot  (1.8  meter),  the  forklift  must  be  equipped 
with long forks. 

 
Reception 

Upon reception, inspect the material to make sure it is 
in good condition before signing the bill of lading or any 
approval document provided by the carrier.  If there is 
damage,  write  it  clearly  on  the  bill  of  lading  or  any 
approval document provided by the carrier.   As soon 
as  possible,  advise  Cadexair  and  provide  pictures  of 
the damaged equipment. 
 
Verify the packing slip attached to the bill of lading to 
make sure all the items listed on the packing slip are 
received.  It is possible that some items are note sent 
in  the  same  shipment.    Refer  to  the  packing  list 
included with the bill of lading for verification. 
 
Claims on missing items must be sent within 72 hours 
following the reception of material.  If claims are done 
after this delay, Cadexair reserves the right to refuse 
the claim. 
 

Storage 

Do not store the exhaust kitchen hood outside; avoid 
exposing the exhaust kitchen hood to the sun and to a 
temperature above 35° Celsius.  These conditions can 
affect  the  adherence  of  the  protective  film  glue 
protecting the exhaust kitchen hood and may damage 
the stainless steel when removing the protective film. 
 
  

 

Installation 

 

IMPORTANT 

Cadexair does not take responsibility for 
the  installation  of  the  exhaust  kitchen 
hood on site unless it is clearly stated in 
the sales contract. 
 
A commercial exhaust kitchen hood must 
always  be  installed  according  to  the 
applicable  NPFA  96  edition  and  local 
standards. 
 
Cadexair  does  not  recommend  walking 
or standing on top of the exhaust kitchen 
hoods.    These  actions  may  damage  and 
deform the exhaust kitchen hood which 
will  void  the  guaranty.    If  an  access  is 
mandatory, installed boards to distribute 
the weight evenly on the exhaust kitchen 
hood joints and not to the center of the 
stainless  steel  sheets.    If  needed, 
additional  supports  must  be  used  to 
support the boards. 

Material clearance  

Make  sure  to  respect  the  clearance  standards  from 
combustible  and  semi-combustible  material.    The 
exhaust  kitchen  hood  must  be  installed  3  inches 
(75mm) from semi-combustible classified material and 
18  inches  (460mm)  from  combustible  material.    This 
clearance standard is applicable to walls, ceiling and 
structural components of the building.  Verify with the 
fabrication plans if clearance reduction methods have 
been applied. 

Kitchen exhaust hood positioning 

Make  sure  to  respect  the  kitchen  exhaust  hood 
homologation  when  installing.    The  hood  must  be 
installed to 78 inches (1980mm) from the finished floor 
in the front.  The exhaust kitchen hood must have an 
overhang  of  6  inches  (150mm)  on  each  side  and  an 

Summary of Contents for CA Series

Page 1: ...User Manual CA Series Version V1 0...

Page 2: ...ds IMPORTANT ATTENTION DANGER A commercial kitchen hood must always be installed by professionals according to the local construction codes in force A commercial kitchen hood ventilation system can ha...

Page 3: ...f the kitchen exhaust hood collar 5 Exhaust hood collar joint and air supply collar joint on PE series 6 Self cleaning hood CA1M series plumbing fitting 6 Electrical wiring 6 Access on top of exhaust...

Page 4: ...exhaust system 9 Inspection and maintenance of the exhaust hood fire suppression system 9 Tips and tricks 10 Problems and solutions 11 ANNEX 1 Exhaust hood weight evaluation table 14 ANNEX 2 Assembly...

Page 5: ...e exhaust kitchen hood to the sun and to a temperature above 35 Celsius These conditions can affect the adherence of the protective film glue protecting the exhaust kitchen hood and may damage the sta...

Page 6: ...haust hood height installation Lift the kitchen exhaust hood and fix the hood with the threaded rods All of the kitchen exhaust hood mounting brackets must be held by a threaded rod Adjust the height...

Page 7: ...he installation and construction is completed Exhaust hood skirting It is possible to install a hood skirting provided by Cadexair or not above the hood The installation method may vary according to t...

Page 8: ...s adding the 5 speed values then divided by 5 Then multiply the average speed value by an effective area factor according to the filters size refer to table below Size Effective Area H x W in SQ FT SQ...

Page 9: ...be used the same way to facilitate the balancing of many exhaust hoods on the same exhaust fan The air flow will adjust according to the opening of the Geo Vary grease extractor If modifications are t...

Page 10: ...ractor Weekly maintenance Remove baffle filters and clean or soak with a hot water and degreaser solution Empty all grease cups located under modular extraction baffles Monthly maintenance Remove and...

Page 11: ...ial kitchen operates usually out of standard working hours evenings and week end It is recommended to have in inventory replacements exhaust and air supply fan motor belts Furthermore for critical com...

Page 12: ...Verify if the magnetic started is powered on the primary side if not verify the power system of the disconnect and the fuse on the distribution panel contact an electrician if needed If the magnetic s...

Page 13: ...ED Clean as fast as possible the suppression liquid Call the company in charge of you fire suppression system maintenance to put the system back in operation If the system is equipped with a rearming...

Page 14: ...50313 01 Installation and maintenance manual www cadexair com 13 1010 Boulevard Lionel Boulet 1 800 461 0668 Varennes Qu bec Canada J3X 1P7 water valves and change them if necessary then contact Cadex...

Page 15: ...1 7 6 1 85 6 5 2 7 2 15 7 5 2 3 8 2 45 8 5 2 6 9 2 75 9 5 2 9 10 3 05 Width CA S 27 12 30 14 33 15 36 16 39 18 42 19 45 20 48 22 Weight CA S PE 50 23 55 25 60 27 65 29 70 32 75 34 80 36 85 39 CA S M...

Page 16: ...dexair com 15 1010 Boulevard Lionel Boulet 1 800 461 0668 Varennes Qu bec Canada J3X 1P7 ANNEX 2 Assembly diagram of an exhaust hood with mecanical joints CA W series NOTE Verify carefully the install...

Page 17: ...t may cause performance issues Cleaning of the Geo Vary grease extractor When necessary remove the Geo Vary from the exhaust hood filter cage carefully noting the guillotine adjustment and position fo...

Page 18: ...ule According to the cooking type Frequency Systems serving solid fuel cooking operations Monthly Systems serving high volume cooking operations such as 24 hour cooking charbroiling or wok cooking Qua...

Reviews: