Operating Your Spa
Page 34
2005 Spa Owner's Manual
8/1/2005
Freeze Protection
If the temperature sensors detect a drop to 44°F within the heater, the pump automatically activates to provide
freeze protection. The equipment stays on until four minutes after the sensors detect that the spa temperature has
risen to 45°F or higher. In colder climates, an optional additional freeze sensor may be added to protect against
freeze conditions that may not be sensed by the standard sensors. Auxiliary freeze sensor protection acts
similarly except with the temperature thresholds determined by the switch and without a four minute delay in
turnoff.
Periodic Reminder Messages
Press the “Mode” button to reset a displayed reminder)
Message Frequency
Action
Require
rPH
Every 7 days
Test and adjust chemical levels per manufacturer’s
instructions.
rSA
Every 7 days
Test and adjust chemical levels per manufacturer’s
instructions.
rCL
Every 30 days
Remove, clean, and reinstall filter per
manufacturer’s instructions.
rtg
Every 30 days
Test and reset GFCI per manufacturer’s instructions.
Drain and refill spa per manufacturer’s instructions.
rdr
Every 90 days
Drain and refill spa per manufacturer’s instructions.
rCO
Every 180 days
Clean and condition spa cover
rCH
Every 365 days
Install New Bio-Clean™ Filter
WARNING! SHOCK HAZARD!
There are no user serviceable parts. DO NOT attempt service of this control system. Contact your dealer
or service center for service.
Diagnostic Messages
Message Meaning
Action
Required
No message on display. Power has
been cut off to the spa.
The control panel will be disabled until power
returns. Spa settings and time of day will be
preserved for 30 days with a battery back-up; settings
only are preserved until the next power-up on 9800
systems.
OHH
“Overheat” - The spa has shut down.
One of the sensors has detected
118°F at the heater.
DO NOT ENTER THE WATER. Remove the spa
cover and allow water to cool. Once the heater has
cooled, reset by pushing any button. If spa does not
reset, shut off the power to the spa and call your
dealer or service organization.
OHS
“Overheat” - The spa has shut down.
One of the sensors has detected that
the spa water is 110°F.
DO NOT ENTER THE WATER. Remove the spa
cover and allow water to cool. At 107°F, the spa
should automatically reset. If spa does not reset, shut
off the power to the spa and call your dealer or
service organization.
Summary of Contents for LTR20051000
Page 1: ...LTR20051000 Rev E 8 1 2005...
Page 72: ...Appendix Figure 33 AUX freeze sensor locations Page 68 2005 Spa Owner s Manual 8 1 2005...
Page 115: ...Appendix Cal Spas Chemicals 2005 Spa Owner s Manual Page 111 8 1 2005...
Page 117: ......
Page 118: ......
Page 119: ......