VIII.4.
Coring of the wall or the ceiling
If the fesh air inlet or/and the exhaust air outlet must pass through a wall, a sufficiently large opening must be provided according
to the recommendations in the following table:
EVERSKY
A mini (mm)
E (mm)
E1 mini (mm)
E2 mini (mm)
Ø mini (mm)
500
190
1300
190
230
300
750
225
1550
225
260
350
900
225
1550
225
260
350
1100
225
1927
225
280
350
Positions of inlet port and exhaust port in frontal or lateral configurations
VIII.5.
Installation et fixation to the ceiling
EVERSKY unit must be installed exclusively indoor, on the ceiling (with or without false ceiling).
Install the unit in such a way that bad weather or ambient temperature cannot damage the internal elements. No water inlet from
outside must be made possible: make sur to install awnings or rain grilles at the fresh air inlet or at the extract air exhaust and to
leave a slight slop from the inside to the outside on the ducts of fresh air supply and extract air discharge.
Make sure to keep the airtight of the building at the core holes between the wall and ducts:
•
On the outside: fill the gap between the duct and the core
•
On the inside: fill the gap between the duct and the core or place a seal between the wall and the face concerned of the
unit.
Before any operation, check that the installation supports are suitable to support the weight of the unit with all accessories and
option.
The mounting bracket must always be attached to the top panel in order to ensure the tightness of the unit.
Support de fixation servant également de gabarit de montage