Chemin d’accès aux paramètres de seuil de CO2
:
Minimum access level:
Operator
Chemin d’accès aux paramètres de vitesse de
ventilateurs :
XIV.6.
Setting the temperature setpoints
The EVERSKY unit offers 4 temperature management modes as standard:
-
Constant supply temperature
-
Variable supply temperature (air law at supply as a function of the outdoor temperature
-
Constant extract temperature
-
Variable extract temperature (air law at extract as a function on the outdoor temperature).
The choice of one or the other of the temperature management mode depends on the presence or absence of a heating/cooling
system in the room and the equipment (electric or water heating coil) present in the EVERSKY unit.
The EVERSKY unit is factory set in variable supply air temperature mode.
Manual/Auto
Settings
Configuration
Access rights
Ctrl CO2/VOC
Fire function
Smoke detector func
Humidity control
CO2/VOC active
If timer on
Type: Fan
Min time: 20 min
Activation level
1/2 speed: 800 ppm
1/1 speed: 1000 ppm
Diff : 160 ppm
Temperature
Air control
Time settings
Access rights
Frequency control
Manual SAF
Output: 70 %
Frequency control
Manual SAF
Output 1/1 : 70%
Output 1/2 : 50%
Frequency control
Manual EAF
Output: 70 %
Frequency control
Manual EAF
Output 1/1 : 70%
Output 1/2 : 50%