26/70
X.2.e.
Performances and operating limits
Maximum length
10m
Maximum elevation
5m
Condensate maximum temperature
+35°C
Overheating thermal protection (automatic
reset)
+115°C
Anti-overflow dry contact
NC (Normally Closed)
8A resistive
–
250Vac
Power consumption
14W
X.2.f.
Installation of condensate lift pump
X.2.f.1. Preliminary checks
Beforehand, check the condensate pan and
pipes for particles (metal chips, plaster/concrete debris…) that may have resulted from
the installation and transport operation and remove them to avoid pump failure.
X.2.f.2. Installation
Step
Description
1
Remove the part of the tube that equips in standard the unit and acting for drainage by gravity.
2
Fix the pump mounting bracket to the pre-drilled wall by means of the 2 metal sheet screws.
3
Install the pump on the mounting bracket and insert the elbow sleeve into the suction connection.