Mounting recommendations of the anti-siphoning device.
X.2.h.
Running test
Following the installation of the pump and its accessories, a test procedure is mandatory to verify the proper operation of the pump
and avoid any inconvenience that could result.
Step
Explanations
1
Clean the condensate pan of any debris (assembly residues, manufacturing residues, packaging residues…) to avoid
premature wear of the pumping system, clogging of the level detection chamber, and a clogging of the pump.
2
Gently pour water into the condensate pan using a bottle.
3
Check that the pump starts and stops properly to evacuate the spilled water.
In the event of too large spill, the overflow safety can be triggered and cut off the electrical supply of the controller.
Wait for the level to drop before allowing the controller to be power again.
X.2.i.
Diagnosis
For any problem, check beforehand:
-
Suction and discharge tubes are not pinched or obstructed
-
The float inside the pump is not blocked
-
The suction and discharge ports of the pump are not obstructed.
Symptoms
Causes and remedies
The pump does not work regardless of the water
level in the tank.
Check the power supply of the pump and wiring.
The pump operates continuously without
shutdown phase and sucks in no/little condensate
level.
Check that the height of discharge does not exceed the maximum allowed
height.
Check the tightness of the suction tube and absence of air intakes.
Replace the pump if necessary.
The pump continuously chains the on/off cycles.
Stop the pump and check the water column in the discharge tube does not
go down. If so, replace the pump.
Other orientations not allowed
a