Setting the fire protection function
The implementation of this function must be validated by a control office.
This function allows you to manage the operation of the supply and extract fans according to 5 modes available in the control
parameters (function can be activated on site):
1. "Stop": Complete shutdown of the unit
2. "Continuous operation": Start or maintain the unit in HS, the fire function will take priority over any other alarm
3. "Normal operation": Maintains the control panel according to the settings made on site (Off/Standby/Standby)
4. "Supply fan only": Start or maintain the supply fan in normal speed (extract off)
5. "extract fan only": Start or maintain the extract fan in normal speed (supply off).
When the fire protection function is activated, an alarm is recorded and the text "Fire alarm" will be displayed on the screen.
The digital input External stop takes precedence over the fire function.
Minimum access level:
Expert/Admin
Path:
Manual/Auto
Settings
Configuration
Access rights
Pump control
Free cooling
Support control
CO2/COV control
Free cool active: Yes
Outd temp activation
22°C
Fan setpoint offset
when free cooling
SAF: 0%
EAF: 0%
Manual/Auto
Settings
Configuration
Access rights
CO2/COV control
Fire function
Smoke detector func
Humidity control
Fire damper function
Not active
Operation when alarm
Stopped
Outdoor airdamper
when fire
Normal function