VIII.5.c.
Installation of the unit in a false ceiling
The unit can be semi-recessed in a false ceiling (mounting (A)) up to 10mm above the blowing grid frame.
(A)
Mounting in contact with the ceiling
(B)
Offset ceiling mounting
The unit can also be offset from the ceiling (B).
In this case, remove the 4 screws (E) M10x70 et replace them with a M10 threaded rod. Allow the threaded rod to protrude 70mm
below the support.
Ensure that the attachment of the threaded rod in the ceiling is strong enough to support:
-
Weight of the unit itself and any options mounted on it
-
Installation loads
-
Operation/maintenance loads
VIII.6.
Access inside the unit
The EVERSKY unit has 3 independent, recessed and hinged doors for access to the interior.
For closing the doors:
1-
Push the door until it is pressed against the seal
located toward the hinges
2-
Raise the door upwards
3-
Turn the locks in the direction of the arrows.