PH
-SERIES
25
ALTERNATIVELY, for models PH-40, PH-50, PH-75,
installer can use material equal to Calcana 3” x 16
gauge sidewall vent kit PIN#800208, c/w 4” x 3” 16 gauge reducer.
NOTE: MAKE SURE THAT ALL FLUE/EXHAUST JOINTS ARE SEALED. USE ONLY SUITABLE PRODUCTS EQUAL TO GENERAL ELECTRIC RTU
106 OR PERMATEX FORM A GASKET RED HIGH TEMPERATURE SILICONE ADHESIVE SEALANT. (NOT SUPPLIED)
D
NOTE: VENT PIPE CAN BE TRIMMED IF NEEDED. CUT EXCESS MATERIAL AS REQUIRED. MAINTAIN 6” (16 cm)
CLEARANCE TO
COMBUSTIBLES. SEAL ALL JOINTS WITH HIGH TEMPERATURE SILICON (SEE PAGE
Error! Bookmark not defined.
).
Figure 15. SIDE WALL VENTING, SINGLE UNIT
NOT
E: Maximum length is 25 feet including, two (2) 90° elbows, deduct 10’ for every additional 90° elbow and
5’ for every 45° elbow.