12
Your Caldera
®
spa has been thoroughly tested during the manufacturing process to ensure reliability and long-term customer satisfaction. A small amount of water may
have remained in the plumbing after testing and, as a result, may have spotted the spa shell or the spa siding prior to delivery. Before filling the spa, clear all debris from
the spa and wipe the spa shell clean with a soft rag.
THE FOLLOWING INSTRUCTIONS MUST BE READ AND FOLLOWED EXACTLY TO ENSURE A SUCCESSFUL START-UP OR REFILL.
CAUTIONS
• Do not fill the spa with hot water, as tripping of the high-limit thermostat may result.
• DO NOT CONNECT POWER TO AN EMPTY SPA. Power to the spa automatically activates critical components within the spa, such as controls,
heater, circulation pump and other systems. If power is supplied to these components prior to the spa being filled, the components will be damaged,
and this may result in a non-warranty component failure.
• Do not use your spa after filling until all of the steps listed below are completed.
• Do not add chlorine if treating your spa with polyhexamethylene biguanide (Biguanide, PHMB, eg. BaquaSpa
®
or Soft Soak
®
) sanitizer.
• Before filling your spa for the first time, remove the equipment compartment doors and check to ensure that the unions on either side of the pump
are hand-tight.
1. Close external drain valve and remove the skimmer basket, weir and filter. Then insert the end of a garden hose into the filter hole and begin filling the spa. The
water level of your Caldera spa should be maintained at a level one inch above the highest jet in the spa. Reinstall the skimmer basket, weir and filter once the spa
is filled.
IMPORTANT:
Watkins
®
Manufacturing Corporation does not recommend that the spa be filled with “softened” water, as this may damage the spa’s equipment.
2.
AFTER
the spa has been filled with water and the equipment compartment door is secured, power must be applied to the spa.
• Activate power to the subpanel from the main house panel first.
• Open the door of the electrical subpanel and reset the GFCI breakers. Close and secure the subpanel door.
3. The jet pump(s), heating system and all internal plumbing will achieve a partial prime as the spa is filled. Five minutes after power is applied to the spa, the air
blower will activate for one minute (except for Martinique
®
and Kauai
®
), followed by Jet Pump 2 (“Jets 2” except for Kauai ) for one minute, followed by Jet Pump 1
(“Jets 1”) for eight minutes. Once the jet system is fully operational (as indicated by strong, non-surging jets), priming of the spa is complete. If you do not feel a
steady stream of water from your jets, refer to the instructions for priming the pump in the SPA TROUBLESHOOTING section in the back of this manual.
IMPORTANT:
Be sure that the air control valves are open by turning each one counterclockwise and checking to see that all the diverters are in position 1 or
position 2 (see illustration on diverter valves).
4. Adjust Total Alkalinity (TA) to 125 ppm, Calcium Hardness (CH) to 150 ppm, then spa water pH to between 7.4 and 7.6. These procedures are listed in the “Water
Quality and Maintenance” section.
OPERATION NOTE:
Adjusting the Total Alkalinity as the first step is important, as out-of balance TA will affect your ability to adjust the pH correctly and will prevent
the sanitizer from operating effectively.
IMPORTANT:
Add spa water chemicals directly over the filter compartment (remove filter lid) with the jet pump on for at least ten minutes (press “CLEAN” button on
the control panel).
5. Superchlorinate the spa water by adding 1-1/2 teaspoons of chlorine (sodium dichlor) per 250 gallons (950 liters) of spa water. When adding chlorine press “CLEAN”
button on the control panel to circulate the spa water for a ten-minute period. Make sure all the diverter valves are set to the middle position.
6. Set the temperature control to the desired temperature between 100°F (38°C) and 104°F (40°C), then place the vinyl cover on the spa and allow the water
temperature to stabilize (approximately 24 hours). Make sure you secure the cover in place using the cover locks. Periodically check the spa water temperature.
When the water temperature climbs above 90°F (32°C), proceed to the next step.
7. Press “CLEAN” button on the control panel, this will run the Jet Pump 1 (Jets 1) for a total of ten minutes to circulate the spa water. Make sure all the diverter valves
are set to the middle position. Once the jets shut off, test the spa water for Free Available Chlorine (FAC) residual. If the residual is between 3 and 5 ppm, go on to
the next step. If the residual is less than 3 ppm, superchlorinate the spa water by adding 1-1/2 teaspoons of chlorine (sodium dichlor) per 250 gallons (950 liters) of
spa water, while the jet pump is running. Press “CLEAN” button on the control panel to circulate the spa water for an additional ten-minute period.
8. Recheck the Total Alkalinity (TA) at 125 ppm, Calcium Hardness (CH) at 150 ppm, then spa water pH at between 7.4 and 7.6.
OPERATION NOTE:
Make sure you adjust your Total Alkalinity first, as an out-of-balance condition will affect your ability to adjust the pH correctly, and will prevent
the sanitizer from operating effectively.
The spa is ready for use when the spa water has circulated and the chlorine level remains between 3 ppm and
5 ppm.
9. The spa temperature is pre-programmed to reach 102°F (39°C), and will normally do so within 18 to 24 hours. You may raise the water temperature by pressing the
“
TEMP
(
▲
)” button on the control panel once to display the temperature, then pressing it again within five seconds to raise the temperature, or lower it by pressing
“
TEMP
(
▼
)” button once to display the temperature, then pressing it again within five seconds to lower the temperature. After a few hours, the water temperature
will remain within 1-1/2 degrees of your selected temperature.
OPERATION NOTE:
For proper water circulation during the ten-minute automatic clean cycle the following steps should be performed.
• Place the diverters valves in the middle (split flow) position.
• Place air control levers in OFF position by rotating clockwise.
START-UP AND REFILL PROCEDURES